Panel Design Calculators
Size the parts of a low-voltage distribution or motor control panel: breakers, fuses, busbars, contactors, DOL and star-delta starters, and VFDs. Each step below shows the NEC (US) rule and the IEC rule that applies.
Motor Calculators
2- VFD Energy Savings CalculatorCalculate VFD energy savings, power reduction, annual electricity cost savings and payback period for motors, pumps and fans using Variable…
- VFD Selection CalculatorCalculate VFD size using IEC 61800-2, IEEE 1566, NEC Article 430, NEMA ICS 7.1 and IEEE 519 based drive engineering recommendations.
Protection Calculators
2Sizing Calculators
6- Breaker Size CalculatorCalculate the correct circuit breaker size for single-phase and three-phase electrical loads.
- Bus Bar Size & Bus Bar Ampacity CalculatorCalculate the recommended copper and aluminum bus bar size, cross-sectional area, width, thickness, and estimated current capacity based on load…
- Contactor Size CalculatorCalculate the recommended contactor size and standard AC3 current rating for single and three-phase electric motors with custom safety factors.
- DOL Starter Component CalculatorCalculate DOL starter components including standard AC-3 contactors, overload relay setting range, MCB/MCCB breakers, control fuses, and cable sizes.
- Star Delta Contactor Size CalculatorCalculate main contactor, delta contactor and star contactor ratings for star-delta starters using motor power and voltage.
- Star Delta Starter Component CalculatorCalculate star delta starter components including main contactor, delta contactor, star contactor, overload relay, MCCB and timer sizing for…
Try a shorter search, such as a unit (kW, GPM) or a device (motor, pump).
What the 10 Calculators Cover
Four groups of tools, one for each type of component in a panel.
Overcurrent Protection (3)
Breaker, fuse and solar PV string fuse ratings from load current, using NEC 240.6(A) standard ratings or IEC 60898-1, IEC 60947-2 and IEC 60269 devices.
Busbars (1)
Copper or aluminium bar size from current, ampacity from bar size and temperature rise, and thermal short-circuit withstand, in metric or inch bars.
Motor Starters (4)
Contactor rating, DOL starter parts, and star-delta main, delta and star contactors with overload relay and short-circuit protection.
Drives (2)
VFD size from motor current and duty, and energy and cost savings for fans and pumps run at reduced speed.
NEC or IEC: Which Rules Apply
In the US the installation follows NFPA 70 (NEC) and the components are UL listed; Canada uses the CSA C22.1 code with similar rules. Most other countries follow IEC 60364 or a national version such as BS 7671, with components to IEC 60947, IEC 60898 and IEC 60269 and assemblies to IEC 61439. The main differences when sizing a panel:
- Motor current: the NEC sizes conductors and short-circuit protection from Table 430.250, not the nameplate (430.6(A)(1)); IEC designs use the motor rated current.
- Continuous loads: the NEC adds 25% (210.20(A), 215.3); IEC 60364-4-43 instead requires Ib ≤ In ≤ Iz and I2 ≤ 1.45 Iz.
- Standard ratings: NEC 240.6(A) lists 15, 20, 25, 30 … A; IEC devices follow the R10 series, such as 6, 10, 16, 20, 25, 32, 40, 50, 63 A.
- Panel short-circuit rating: SCCR to UL 508A Supplement SB, marked under NEC 409.110; IEC 61439 assemblies state Icw, Ipk or a conditional Icc.
Breaking Capacity
Every breaker and fuse must interrupt the prospective fault current at its location: Icu / Ics to IEC 60947-2 or Icn to IEC 60898-1; interrupting rating under NEC 110.9.
Starter Coordination
IEC 60947-4-1 Type 2 coordination means the contactor and overload relay remain usable after a short circuit; Type 1 allows damage. Use the maker's tested combinations.
Assembly Verification
Calculated sizes are a starting point. The finished panel is verified for temperature rise and short-circuit withstand to IEC 61439-1, or built and listed to UL 508A, UL 891 or UL 67.
Panel Design Workflow
The order in which the calculators are used, with the NEC and IEC rule for each step.
1. Find the Design Current
Motor full-load current: NEC Table 430.250 (430.6(A)(1)); IEC: motor nameplate. For other loads, I = P ÷ (√3 × V × PF) three-phase. The breaker, contactor, DOL, star-delta and VFD calculators all start here.
2. Select the Protective Device
Breaker and fuse calculators. NEC: 125% of continuous load, next rating in 240.6(A), Table 430.52 for motor circuits. IEC: Ib ≤ In ≤ Iz, curve B, C or D (IEC 60898-1), gG or aM fuses (IEC 60269). For PV strings, the solar panel fuse calculator applies NEC 690.8 / 690.9 or IEC 62548 gPV fuses.
3. Size the Motor Starter
Contactor, DOL and star-delta calculators. IEC: AC-3 rating to IEC 60947-4-1, overload relay at motor rated current. NEC: controller rating (430.83), overload at 115–125% of nameplate (430.32), disconnect at 115% of FLC (430.110). In star-delta, main and delta contactors carry 58% and the star contactor 33% of motor current.
4. Select the Drive
VFD selection: choose by output current at the load's duty (normal or heavy), to IEC 61800-2; NEC input conductors at 125% of the drive's rated input current (430.122). VFD energy savings then estimates the saving for centrifugal fans and pumps.
5. Size the Busbar and Verify the Panel
Busbar calculator: bar size from current density, ampacity at the real temperature rise, and thermal withstand. Then confirm the panel short-circuit rating against the available fault current: IEC 61439-1 Icw, or NEC 110.10, 408.6 and 409.110 SCCR.
Key Panel Design Formulas
The relationships the calculators are built on.
NEC 210.20(A) and 215.3, then round up to the next standard rating in 240.6(A).
IEC 60364-4-43. Breakers to IEC 60898-1 and IEC 60947-2 meet the second condition when In ≤ Iz.
A in mm², J = current density (about 1.5 A/mm² copper, 1.0 A/mm² aluminium as a starting point), F = design factor. Confirm the result by temperature rise.
Phase current is In ÷ √3. Starting current and torque in star are one third of the DOL values.
At 80% speed the ideal shaft power is 51% of full. Real savings are lower where there is static head or fixed system pressure.
Can't Find the Calculator You Need?
Tell us what you are working on and we will add it, or browse all 400+ engineering calculators.
Common Panel Design Questions
Short answers on breaker sizing, busbars, starters, panel short-circuit ratings and drives.
How do you size a circuit breaker under the NEC and under IEC rules?
NEC: rate the breaker at least 125% of the continuous load plus 100% of the non-continuous load (210.20(A), 215.3), round up to the next standard rating in 240.6(A), and check that it protects the conductor (240.4). For a motor branch circuit, Table 430.52 allows an inverse-time breaker up to 250% of the Table 430.250 full-load current.
IEC: choose a rated current In between the design current Ib and the cable capacity Iz (IEC 60364-4-43), pick curve B, C or D to suit inrush, and check that the breaking capacity is at least the prospective fault current.
What is the current carrying capacity of a copper busbar?
It depends on cross-section, temperature rise, surface and enclosure. A design density of about 1.5 A/mm² is a common starting size. For example, the busbar calculator estimates about 577 A for a single bare 40 × 10 mm copper bar in free air at a 30 K rise (AC), and about 78% of that for aluminium of the same size. Under IEC 61439-1 the final rating comes from temperature-rise verification; NEC 366.23(A) limits bare copper bars in auxiliary gutters to 1000 A/in² (1.55 A/mm²).
What is the difference between DOL and star-delta starters?
A DOL starter connects the motor straight to the supply, so starting current is typically 5 to 8 times full-load current.
A star-delta starter starts the motor in star, which cuts starting current and torque to one third of the DOL values, then switches to delta. The main and delta contactors carry 58% of motor current and the star contactor about 33%, so they can be smaller than a DOL contactor. The motor must be rated for delta at the supply voltage (for example 400 V delta on a 400 V supply).
What is SCCR, and how does it compare with Icu?
SCCR (short-circuit current rating) is the fault current a US industrial control panel can withstand; NEC 409.110 requires it on the nameplate, and UL 508A Supplement SB is the common way to find it. It must be at least the available fault current (NEC 110.10).
Icu and Ics are the ultimate and service breaking capacities of a single circuit-breaker under IEC 60947-2. An IEC 61439 assembly is rated separately, by its short-time withstand Icw, peak Ipk or conditional short-circuit current Icc.
How does a VFD save energy?
On centrifugal fans and pumps, shaft power falls with the cube of speed, so running at 80% speed needs about 51% of full-speed power in the ideal case. Savings are smaller for systems with static head, and nearly zero for constant-torque loads such as conveyors run at full speed. The drive itself has losses, which the VFD energy savings calculator includes.
Explore More Calculators
Expand your engineering toolkit with these related calculator categories.