Transformer Inrush Current Calculator

Calculate peak inrush current and protection requirements for power transformers

Transformer Inrush Current Calculator

Compliant with IEEE C57.12.00 & IEC 60076 Standards

Results:

Full Load Current: 0.00 A

Peak Inrush Current: 0.00 A

Inrush Duration: 0.1 - 1.0 sec

Protection Setting: 0.00 A

How to Use the Transformer Inrush Current Calculator

Step 1: Select Transformer Type

  1. Choose your transformer type from the dropdown
  2. Power transformers: 8-12x inrush factor
  3. Distribution transformers: 12-20x inrush factor
  4. Dry type transformers: 6-10x inrush factor
  5. Select "Custom" for specific inrush factors

Step 2: Enter Transformer Data

  1. Select phase configuration (Single or Three Phase)
  2. Enter transformer kVA rating
  3. Input primary voltage (line-to-line for 3-phase)
  4. Verify the inrush factor is appropriate
  5. Click "Calculate" to get results

Step 3: Interpret Results

  1. Full Load Current: Normal operating current
  2. Peak Inrush Current: Maximum transient current
  3. Inrush Duration: Time for current to stabilize
  4. Protection Setting: Recommended overcurrent setting
  5. Use results for protection coordination

How to Calculate Transformer Inrush Current

Understanding Inrush Current

Transformer inrush current occurs when:

  • Transformer is first energized
  • Magnetic flux asymmetry develops
  • Core saturation causes high current
  • Current gradually decreases to normal

Calculation Steps

  • Calculate Full Load Current (FLC)
  • Determine appropriate inrush factor
  • Multiply FLC by inrush factor
  • Consider protection coordination

Key Formulas:

Single Phase FLC: I = kVA × 1000 / V

Three Phase FLC: I = kVA × 1000 / (√3 × V)

Inrush Current: I_inrush = K × I_FLC

Real-Life Calculation Example

Given: 500 kVA, 11kV/415V, Three-phase Distribution Transformer

Step 1: Calculate Primary Full Load Current

I_primary = 500 × 1000 / (√3 × 11000) = 26.24 A

Step 2: Calculate Secondary Full Load Current

I_secondary = 500 × 1000 / (√3 × 415) = 695.7 A

Step 3: Apply Inrush Factor (K = 15 for distribution transformer)

Primary Inrush = 15 × 26.24 = 393.6 A

Secondary Inrush = 15 × 695.7 = 10,435.5 A

Step 4: Protection Setting (typically 1.25 × FLC)

Primary Protection = 1.25 × 26.24 = 32.8 A

Secondary Protection = 1.25 × 695.7 = 869.6 A

Result: Peak inrush current is 393.6 A on primary side, lasting 0.1-1.0 seconds

Calculation Formulas

Single Phase FLC:
I = kVA × 1000 / V

Three Phase FLC:
I = kVA × 1000 / (√3 × V)

Inrush Current:
I_inrush = K × I_FLC

Protection Setting:
I_protection = 1.25 × I_FLC

Typical Inrush Factors

  • Power Transformers: 8-12 times FLC
  • Distribution Transformers: 12-20 times FLC
  • Dry Type Transformers: 6-10 times FLC
  • Current Transformers: 20-40 times FLC
  • Small Transformers (<10kVA): 25-40 times FLC

Factors Affecting Inrush Current

  • Transformer core material and design
  • Switching angle (worst at voltage zero)
  • Residual flux in the core
  • System impedance
  • Transformer size and rating

Related Transformer Calculators

Transformer Short Circuit Current Calculator

Calculate fault current and impedance

Try Calculator

kVA Calculator

Power rating calculations

Try Calculator

kVA to HP Converter

Convert between power units

Try Calculator