Zs Calculator
Calculate the maximum permitted earth fault loop impedance (Zs) according to BS 7671 wiring regulations. Compare measured values to corrected design limits for automatic disconnection compliance.
BS 7671 Zs Calculator
How to Use Zs Calculator
Verifying earth fault loop impedance is a critical inspection and testing requirement for verifying electrical safety in UK installations.
-
1Select protective device type. Choose the installed circuit breaker type (Type B, C, or D MCB) or standard UK fuse (BS 88, BS 1361, or BS 3036 rewirable).
-
2Select rated current. Pick the rating of the protective device (In) in Amps.
-
3Select disconnection time. For fuses, choose the required automatic disconnection time (0.4s for final circuits under 32A, or 5s for distribution boards and large circuits).
-
4Enter nominal voltage and correction factors. Verify Uo is set to the UK nominal voltage (typically 230V) and keep the BS 7671 voltage correction factor (Cmin) at its default of 0.95.
-
5Enter measured Zs if available. Input the loop impedance value measured with your multifunction tester at the furthest point of the circuit.
-
6Compare measured and permitted values. Review the compliance card to verify if the measured Zs complies with the corrected design limit.
Practical UK Inspection & Testing Example
During an inspection of a commercial final circuit supplying double socket-outlets, the protective device is identified as a Type B 32A MCB. The nominal supply voltage is 230V and a voltage factor of 0.95 is used. The inspector performs a loop impedance test at the end of the line and records a measured Zs of 1.12 Ω. The maximum Zs in BS 7671 Table 41.3 is 1.37 Ω (230 V × 0.95 ÷ 160 A). That limit applies with conductors at their maximum operating temperature, so a cold measured value is compared with 80% of it: 1.37 × 0.8 = 1.10 Ω. The measured 1.12 Ω is above 1.10 Ω, so the result is a FAIL. The inspector should check the connections and the R1+R2 value, or consider an RCD or a larger protective conductor.
How to Calculate Zs
Earth fault loop impedance (Zs) calculations ensure that during a fault to earth, the prospective fault current is high enough to trip the circuit protective device before a dangerous touch voltage can cause electric shock. Sizing and verification follows standard mathematical relationships defined by the IET Wiring Regulations.
The Earth Fault Loop Formula
The total loop impedance of a circuit is calculated as the sum of external supply path impedance and conductor resistance:
Where:
- Zs = total loop impedance at the furthest point of the circuit (Ω)
- Ze = external earth loop impedance at the origin of the installation (Ω)
- R1 = resistance of the phase (line) conductor (Ω)
- R2 = resistance of the circuit protective conductor (CPC) (Ω)
Determining Maximum Permitted Zs
To guarantee that the protective device trips automatically, the loop impedance must satisfy the disconnection current requirements:
Where:
- Uo = nominal AC voltage to earth (230V in the UK)
- Cmin = minimum voltage factor (0.95 per BS 7671:2018)
- Ia = current causing automatic disconnection within the required time (e.g., 5s or 0.4s)
Worked Example: Type B 32A MCB
Let's calculate the maximum permitted and corrected design loop impedance for a Type B 32A miniature circuit breaker:
Step 1 — Calculate Disconnection Current (Ia)
For Type B MCBs, instantaneous tripping occurs at 5 times the rated current (In). So:
Step 2 — Calculate Maximum Zs (BS 7671 Table 41.3)
Using the nominal voltage Uo = 230V and the minimum voltage factor Cmin = 0.95:
Step 3 — Apply the 80% Rule for Measured Values
Testing is done with cold conductors, which have lower resistance than at operating temperature. The common rule of thumb (IET Guidance Note 3) is to compare measured values with 80% of the tabulated maximum:
Final Answer
The maximum Zs for a B32 MCB is 1.37 Ω, and a measured (cold) reading should not exceed 1.10 Ω.
Why Correction Factors are Applied in UK Installations
Tabulated Zs values in BS 7671 represent the maximum permissible limits when cables are at their maximum operating temperature (70°C for thermoplastic/PVC insulated cables). However, testing is carried out at ambient temperature (typically 10°C to 20°C) when conductors are cold and have lower resistance. To ensure that the loop impedance will not rise above the safe limit when the cables heat up under load, engineers apply the 80% rule of thumb during on-site tests, after the tabulated limits have already been reduced by Cmin = 0.95 for the worst-case supply voltage.
Zs Chart
This table lists the maximum permitted earth loop impedance (Zs) for standard Type B, Type C, and Type D MCBs at UK nominal supply voltage (230V): Uo ÷ Ia without Cmin, the BS 7671 Table 41.3 maximum with Cmin = 0.95, and the 80% limit for measured values.
| Device Type | Rating (In) | Uo ÷ Ia (no Cmin) | Table 41.3 Max Zs | Max Measured (80%) |
|---|---|---|---|---|
| Type B MCB (BS EN 60898) | 6A | 7.67 Ω | 7.28 Ω | 5.82 Ω |
| Type B MCB (BS EN 60898) | 10A | 4.60 Ω | 4.37 Ω | 3.50 Ω |
| Type B MCB (BS EN 60898) | 16A | 2.88 Ω | 2.73 Ω | 2.18 Ω |
| Type B MCB (BS EN 60898) | 20A | 2.30 Ω | 2.19 Ω | 1.75 Ω |
| Type B MCB (BS EN 60898) | 32A | 1.44 Ω | 1.37 Ω | 1.10 Ω |
| Type B MCB (BS EN 60898) | 40A | 1.15 Ω | 1.09 Ω | 0.87 Ω |
| Type B MCB (BS EN 60898) | 63A | 0.73 Ω | 0.69 Ω | 0.55 Ω |
| Type C MCB (BS EN 60898) | 6A | 3.83 Ω | 3.64 Ω | 2.91 Ω |
| Type C MCB (BS EN 60898) | 10A | 2.30 Ω | 2.19 Ω | 1.75 Ω |
| Type C MCB (BS EN 60898) | 16A | 1.44 Ω | 1.37 Ω | 1.10 Ω |
| Type C MCB (BS EN 60898) | 20A | 1.15 Ω | 1.09 Ω | 0.87 Ω |
| Type C MCB (BS EN 60898) | 32A | 0.72 Ω | 0.68 Ω | 0.54 Ω |
| Type C MCB (BS EN 60898) | 40A | 0.58 Ω | 0.55 Ω | 0.44 Ω |
| Type C MCB (BS EN 60898) | 63A | 0.37 Ω | 0.35 Ω | 0.28 Ω |
| Type D MCB (BS EN 60898) | 6A | 1.92 Ω | 1.82 Ω | 1.46 Ω |
| Type D MCB (BS EN 60898) | 10A | 1.15 Ω | 1.09 Ω | 0.87 Ω |
| Type D MCB (BS EN 60898) | 16A | 0.72 Ω | 0.68 Ω | 0.54 Ω |
| Type D MCB (BS EN 60898) | 20A | 0.58 Ω | 0.55 Ω | 0.44 Ω |
| Type D MCB (BS EN 60898) | 32A | 0.36 Ω | 0.34 Ω | 0.27 Ω |
| Type D MCB (BS EN 60898) | 40A | 0.29 Ω | 0.27 Ω | 0.22 Ω |
| Type D MCB (BS EN 60898) | 63A | 0.18 Ω | 0.17 Ω | 0.14 Ω |
Always verify values against the latest edition of BS 7671 and device manufacturer documentation to ensure full safety compliance.
Zs Calculator Frequently Asked Questions
In electrical installations, Zs is the total earth fault loop impedance of a circuit. It is the sum of the external path impedance (Ze) and the resistance of the circuit line and protective conductors (R1 + R2) from the origin to the furthest point of the circuit. A low Zs is important to ensure that enough fault current flows to trip the protective device quickly during a fault.
Maximum Zs is the highest allowable earth fault loop impedance for a specific protective device to ensure automatic disconnection of the electrical supply within the time limits specified by BS 7671 (e.g., 0.4 seconds for final circuits or 5 seconds for distribution circuits). If the actual circuit loop impedance exceeds this maximum value, the protective device may not operate in time, creating a shock risk.
Zs is measured using an earth loop impedance tester (often part of a multifunction tester). The test is performed at the furthest point of the circuit with the supply energized. The tester connects to the line, neutral, and earth terminals and draws a brief current to measure the loop resistance. It can be measured directly or calculated as the sum of Ze and the measured (R1 + R2).
Ze is the external earth fault loop impedance. It represents the impedance of the supply network up to the origin of the installation (usually the consumer unit or distribution board). Ze includes the resistance of the substation transformer windings, the line conductor of the distributor network, and the earth return path (which varies depending on the earthing system: TN-C-S, TN-S, or TT).
BS 7671 incorporates a voltage factor, Cmin, which is typically 0.95 for UK 230V/400V installations. This factor accounts for fluctuations in the mains supply voltage. By multiplying the nominal voltage (Uo) by Cmin, we calculate a lower minimum fault current, which translates to a safer, lower maximum permitted Zs value. This ensures the circuit remains safe even when the supply voltage drops slightly.
If Zs is too high, the prospective earth fault current will be too low. Consequently, during a line-to-earth fault, the protective device (fuse or circuit breaker) will take too long to disconnect the supply, or might not trip at all. This leaves metallic parts of the installation energized at a dangerous touch voltage, creating a severe risk of electric shock and potential electrical fires.