Star Delta Motor Cable Size Calculator

Calculate the required copper or aluminum cable size for three-phase star-delta motor installations based on motor power, voltage, run length, voltage drop limit, temperature derating, and safety margins.

By Nadeem Sial, Senior Electrical EngineerUpdated

Star Delta Motor Cable Size Calculator

%
m

How to Use Star Delta Motor Cable Size Calculator

Determining the correct conductor cross-section for a star-delta starter motor circuit is important for safe operational runs. Since star-delta starting splits the load current between two separate paths between the starter panel and the motor terminals, different sizing constraints apply for delta running and star starting stages.

  • 1
    Input Motor Power. Enter the rated motor shaft power from the nameplate and choose the correct units (kW or HP).
  • 2
    Select Supply Voltage. Select the line-to-line operating voltage of your three-phase system (e.g. 415 V).
  • 3
    Enter Electrical Parameters. Input the motor's nominal power factor (cos phi) and efficiency percentage.
  • 4
    Choose Conductor Material & Installation Method. Select Copper or Aluminum and how the cable runs will be installed (Conduit, Tray, etc.).
  • 5
    Enter Cable Length & Ambient Temp. Input the continuous distance between starter and motor and select local temperature.
  • 6
    Specify Voltage Drop Limit & Safety Factor. Choose the allowable drop limit (typically 3%) and safety margin factor.

How to Calculate Star Delta Motor Cable Size

Calculating the required cable sizes for star-delta motor installations involves sizing the conductors based on the winding current rather than the total line current. In a star-delta configuration, two separate three-core cables run from the starter panel to the six motor terminals. Both cables carry the same winding current: 58% (1/√3) of the full load line current during delta running, and the star starting current (one third of the DOL starting current) for the few seconds of star starting. Both cables are therefore the same size, selected on the continuous delta running current. Here is the step-by-step sizing math:

Step 1 — Calculate Full Load Current (FLC)

Calculate the three-phase full load line current (IFLC) drawn by the electric motor using rated power, line-to-line voltage, power factor, and efficiency:

IFLC = (P × 1000) / (√3 × V × PF × η)

Step 2 — Determine Cable Winding Current (Phase Current)

Because the star-delta starter panel routes the current through two separate paths to the motor terminal box, both cables carry the delta phase current (Idelta) during normal running and the star starting current (Istar) during starting. Istar lasts only a few seconds, so both cables are sized on Idelta; Istar is used to check the voltage drop during starting (assuming a DOL starting current of 6 × FLC):

Idelta = IFLC / √3 ≈ 0.58 × IFLC
Istar = IDOL start / 3 ≈ (6 × IFLC) / 3 = 2 × IFLC

Step 3 — Apply Safety Factor for Design Currents

Multiply the delta running current by the chosen safety factor (e.g., 1.15 or 1.25) to determine the design current used for selecting the size of both cables:

Design Current = Idelta × Safety Factor

Step 4 — Verify Sizing Against Voltage Drop (VD)

Using standard linear resistance values (R), calculate the running and starting voltage drop along the run for both connections. Ensure the running drop remains within the specified limit (e.g., 3%); the short starting drop is normally allowed to be higher:

VDdelta (V) = (√3 × Idelta × Length × R) / 1000
VDstar (V) = (√3 × Istar × Length × R) / 1000

Step-by-Step Worked Sizing Example

Given Parameters:

  • Motor Output Power: 30 kW
  • System Voltage (Line-to-Line): 415 V
  • Operating Power Factor: 0.85
  • Motor Efficiency: 90% (0.90)
  • Cable Length: 60 m
  • Conductor Material: Copper (in Conduit)
  • Ambient Temperature: 30°C
  • Safety Factor: 1.15

Step 1 — Compute Full Load Line Current (FLC)

IFLC = 30000 / (1.73205 × 415 × 0.85 × 0.90) = 30000 / 549.88 = 54.56 A

Step 2 — Compute Cable Delta and Star Currents

Idelta = 54.56 A / 1.73205 = 31.50 A (58% of FLC, both cables while running)

Istar = 2 × 54.56 A = 109.11 A (both cables, for a few seconds during star starting)

Step 3 — Compute Cable Design Currents

Design Current = 31.50 A × 1.15 = 36.22 A

Step 4 — Select Cable Sizes by Ampacity

Looking up the standard IEC conduit ampacity table for copper at 30°C:

  • For Delta (Design Current 36.22 A): 6 mm² copper carries 34 A (fails), 10 mm² copper carries 46 A (passes). So, the minimum delta size by ampacity is 10 mm².
  • For Star: the second cable carries the same winding current, so it is also 10 mm².

Step 5 — Verify Cable Sizes by Voltage Drop

Using copper linear resistance values (10 mm² = 1.83 Ω/km):

  • For Delta Run (10 mm²): VD = (1.732 × 31.50 A × 60 m × 1.83) / 1000 = 5.99 V. Drop % = (5.99 V / 415 V) × 100 = 1.44% (passes ≤ 3%).
  • During Star Starting (10 mm²): VD = (1.732 × 109.11 A × 60 m × 1.83) / 1000 = 20.75 V. Drop % = (20.75 V / 415 V) × 100 = 5.00% (short-time starting drop).

Thus, the final recommended sizes are 10 mm² for both motor cables (U1-V1-W1 and U2-V2-W2).

Star Delta Motor Cable Size Chart

This reference chart lists approximated motor full load currents and recommended copper and aluminum cable sizes for star-delta motor starting systems. Sizing is based on 415V supply, 0.85 power factor, 90% motor efficiency, conduit routing at 30°C, a safety margin of 1.15, and short runs where voltage drop does not govern. Both motor cables carry the same winding current, so the delta and star cables are the same size.

Motor Power (kW) Approx FLC (A) Copper Cable (Delta / Star) Aluminum Cable (Delta / Star) Typical Application
1.5 kW 2.7 A 1.5 / 1.5 mm² 1.5 / 1.5 mm² Small blowers, exhaust fans
3.0 kW 5.5 A 1.5 / 1.5 mm² 1.5 / 1.5 mm² Small centrifugal pumps, conveyors
5.5 kW 10.0 A 1.5 / 1.5 mm² 1.5 / 1.5 mm² Small air compressors, packaging machines
7.5 kW 13.6 A 1.5 / 1.5 mm² 1.5 / 1.5 mm² Workshop machinery, commercial fans
11.0 kW 20.0 A 1.5 / 1.5 mm² 2.5 / 2.5 mm² Industrial mixers, medium pumps
15.0 kW 27.3 A 2.5 / 2.5 mm² 4.0 / 4.0 mm² Machine tools, medium compressors
22.0 kW 40.0 A 6.0 / 6.0 mm² 10.0 / 10.0 mm² Large ventilation systems, heavy conveyors
30.0 kW 54.6 A 10.0 / 10.0 mm² 16.0 / 16.0 mm² Water supply pumps, industrial compressors
37.0 kW 67.3 A 10.0 / 10.0 mm² 16.0 / 16.0 mm² Crushers, heavy-duty mixers
45.0 kW 81.8 A 16.0 / 16.0 mm² 25.0 / 25.0 mm² Industrial refrigeration compressors, mills
55.0 kW 100.0 A 25.0 / 25.0 mm² 35.0 / 35.0 mm² Heavy draw fans, water treatment pumps
75.0 kW 136.4 A 35.0 / 35.0 mm² 50.0 / 50.0 mm² Large hydraulic systems, mining pumps
90.0 kW 163.7 A 50.0 / 50.0 mm² 70.0 / 70.0 mm² Extruders, heavy processing machinery
110.0 kW 200.0 A 70.0 / 70.0 mm² 95.0 / 95.0 mm² Industrial shredders, heavy pumps
132.0 kW 240.1 A 95.0 / 95.0 mm² 120.0 / 120.0 mm² Large steel mills, high-capacity compressors

Note: Values are approximate, sized for delta / star configurations. Actual installation conditions, bundling grouping factors, voltage drop limits, and local codes must always be checked to ensure safety and code compliance.

Star Delta Motor Cable Size Calculator Frequently Asked Questions

Sizing cables for a star-delta motor involves calculating the motor's full load line current (FLC) and dividing it by the square root of 3 (1.732) to find the phase winding current (~58% of FLC). Each of the two run cables must be sized to carry this phase current, adjusted for ambient temperature, installation routing, and voltage drop constraints.

Yes. Since a star-delta starter splits the load across two separate 3-core cables running to the motor terminals, each cable carries only the phase current (58% of FLC) rather than the full line current. Consequently, the conductor cross-section for each run can be smaller than a single cable used in Direct-On-Line starting.

For a standard 30 kW, three-phase 415V motor with a star-delta starter, the full load current is approximately 54.6 A. The phase current carried by each of the two cables is about 31.5 A. Sized under conduit conditions at 30°C, a 10 mm² copper cable is typical, whereas a Direct-On-Line starter would require a 16 mm² or 25 mm² supply cable.

Absolutely. Long cable runs accumulate electrical resistance, leading to terminal voltage drops. Standard electrical guidelines (like NEC or IEC) recommend limiting motor branch circuit voltage drops to 3% or less. If calculations show a higher drop, a larger conductor size must be selected to maintain motor efficiency and torque.

Yes, aluminum cables can be used, but since aluminum has lower conductivity than copper, you must size up the conductors to achieve the same current rating and voltage drop performance. Typically, an aluminum cable needs to be about one to two standard sizes larger than its copper counterpart for the same motor load.

Cable length is directly proportional to loop resistance. As the distance between the starter panel and the motor increases, the voltage drop along the cable rises. To keep the voltage drop within the acceptable limit (typically 3%), you must increase the cross-sectional area of the cable, even if the thermal current rating is already satisfied.

Standards and References

The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.

Nadeem Sial

Nadeem Sial

Senior Electrical Engineer

This calculator and technical guide were developed and verified by Nadeem Sial to ensure engineering and calculation precision. View Full Profile →

Related Calculators

Motor

Star Delta Motor Current Calculator

Calculate star and delta motor currents instantly using motor power, voltage, efficiency and power factor.

Open calculator
Panel Design

Star Delta Contactor Size Calculator

Calculate main contactor, delta contactor and star contactor ratings for star-delta starters using motor power and voltage.

Open calculator
Motor

Motor Cable Size Calculator

Calculate the minimum cable size for single and three-phase electric motors.

Open calculator