BusBar Amps Calculator

Determine the current capacity of busbars

BusBar Amps Calculator

Compliant with IEC 61439 & NEC Article 368 Principles

Busbar Specifications


Environmental Conditions


System Parameters

Results:

Total Area (A_total): 0.00 mm²

Current Density (J): 0.00 A/mm²

Base Current (I_base): 0.00 A

Proximity Factor (Kp): 0.00

Env. Factor (Kenv): 0.00

Rated Current (I_rated): 0.00 A


Short-Circuit (I_th): 0.00 kA

Resistance (R): 0.00

Total Power Loss (P_total): 0.00 W

Est. Load Power (P): 0.00 kW

How to Use the Calculator

1. Enter Busbar Specs

  1. Enter the Width (mm) and Thickness (mm) of a single busbar.
  2. Input the Number of Bars used in parallel for each phase.
  3. Select the busbar Material (Copper or Aluminum).

2. Define Conditions

  1. Choose the Enclosure Type to determine the base current density (J).
  2. Select the Bar Spacing to set the proximity effect factor (Kp).
  3. Enter the Ambient Temperature and Altitude to find the environmental correction factor (Kenv).

3. Set System Parameters

  1. Enter the Busbar Length (m) to calculate resistance and power loss.
  2. Input System Voltage and Power Factor to estimate the total load power (kW).
  3. Set the Fault Duration (s) (typically 1s) to find the short-circuit withstand capacity.

How to Calculate Busbar Amps from Size (as per IEC & NEC)

Step 1 – Define Inputs

Start by gathering these values:

  • Busbar width (W) in mm
  • Busbar thickness (T) in mm
  • Number of bars (Nbars)
  • Material (Cu or Al)
  • Ambient temperature (Ta)
  • Spacing (S) & Enclosure
  • System voltage (V)

Step 2 – Calculate Area

The area of one bar is:

A = W × T

For multiple bars per phase:

A_total = A × Nbars

Example (80x10mm):

A = 80 × 10 = 800 mm²

Step 3 – Get Base Current

Base current depends on current density (J):

  • Cu (enclosed): ~1.3 A/mm²
  • Cu (ventilated): ~2.0 A/mm²
  • Al (enclosed): ~1.0 A/mm²

I_base = A_total × J

Example (Cu, enclosed):

I_base = 800 × 1.3 = 1040 A

Step 4 – Apply Corrections

(a) Proximity (Kp):

  • Spacing ≈ T: Kp = 0.90
  • Spacing ≥ T: Kp = 0.95
  • Stacked: Kp = 0.85

(b) Environment (Kenv):

Derate for Ta > 40°C or Altitude > 1000m.

I_rated = I_base × Kp × Kenv

Example:

I_rated = 1040 × 0.90 × 1.0 = 936 A

Step 5 – Check Short-Circuit

The thermal withstand (1s) is:

I_th(1s) = k × A_total

  • k = 80 (Copper)
  • k = 55 (Aluminum)

For 't' seconds:

I_th(t) = I_th(1s) ÷ √t

Example (Cu, 1s):

I_th(1s) = 80 × 800 = 64,000 A (64 kA)

Step 6 – Find Resistance

Use resistivity (ρ) at 90°C:

  • Cu: ρ = 0.021 Ω·mm²/m
  • Al: ρ = 0.034 Ω·mm²/m

R = (ρ × L) ÷ A_total

Example (1m Cu):

R = (0.021 × 1) ÷ 800

R = 0.00002625 Ω

Step 7 – Find Power Loss

Power loss per phase (using I_rated):

P_loss = I_rated² × R

Total 3-phase loss:

P_total = 3 × P_loss

Example (Cu):

P_loss = 936² × 0.00002625 = 22.9 W

P_total = 3 × 22.9 = 68.7 W

Step 8 – Estimate Load Power

The 3-phase load (kW) is:

P(kW) = √3 × V × I_rated × PF ÷ 1000

Example (400V, 0.9 PF):

P = 1.732 × 400 × 936 × 0.9 ÷ 1000

P = 584 kW

Step 9 – Final 80x10mm Rating

A single 80x10mm Copper bar (enclosed, 40°C) is rated for:

  • Area: 800 mm²
  • Rated Amps: 936 A
  • Short-Circuit: 64 kA (1s)
  • Load @ 400V: ~584 kW

Note: Always verify with manufacturer data. These are estimates based on IEC/NEC principles.

Busbar Amp Chart (Typical Ratings)

This table shows approximate ampacities for common busbar sizes based on the formulas above (enclosed, 40°C, Kp=0.9).

Busbar Size (W x T) (mm) Busbar Area (mm²) Estimated Busbar Amps (A) Material
40 x 10 mm 400 mm² ~468 A Copper
60 x 10 mm 600 mm² ~702 A Copper
80 x 10 mm 800 mm² ~720 A Aluminum
80 x 10 mm 800 mm² ~936 A Copper
100 x 10 mm 1000 mm² ~1170 A Copper

FAQs

1. How to calculate busbar amps?

To calculate busbar amps, first find the busbar’s cross-sectional area using the formula A = Width × Thickness. Then multiply by the current density, which depends on the material and environment. For example, use I = A × J, where J is about 1.3 A/mm² for copper in an enclosed setup. Apply correction factors for proximity and temperature, using I_rated = A × J × Kp × Kenv. Example: an 80×10 mm copper bar gives I = 80 × 10 × 1.3 × 0.9 = 936 A.

2. What size is a 400 amp busbar?

To size a busbar for 400 A, reverse the formula: A_required = I ÷ (J × Kp × Kenv). For copper at 1.3 A/mm², Kp = 0.9, Kenv = 1.0, you get A_required = 400 ÷ (1.3 × 0.9) = 342 mm². A practical size is 40×10 mm (400 mm²), which easily carries 400 A.

3. What size is a 600 amp busbar?

Using the same method, A_required = 600 ÷ (1.3 × 0.9) = 513 mm². A 60×10 mm copper bar (600 mm²) fits this rating. The expected current capacity is I = 600 × 1.3 × 0.9 = 702 A, giving safe headroom above 600 A.

4. What size is a 800 amp busbar?

Calculate required area as A_required = 800 ÷ (1.3 × 0.9) = 684 mm². The nearest standard bar is 80×10 mm (800 mm²). The estimated capacity is I = 800 × 1.3 × 0.9 = 936 A, which comfortably handles 800 A continuous.

5. What size busbar is needed for 1000 amps?

For a 1000 A copper busbar, A_required = 1000 ÷ (1.3 × 0.9) = 854 mm². You can use a single 100×10 mm bar (1000 mm²) or two 50×10 mm bars in parallel per phase. The calculated ampacity is I = 1000 × 1.3 × 0.9 = 1170 A, ensuring reliable performance and compliance with IEC 61439 and NEC 368 guidelines.

Related Power Calculators

Star-Delta Contactor Size Calculator

Size contactors for star-delta motor starters

Try Calculator

Solar Panel Fuse Size Calculator

Calculate fuse sizes for solar PV systems

Try Calculator

DOL Starter Component Calculator

Size components for Direct Online motor starters

Try Calculator