DOL Starter Component Calculator
Size the parts of a direct-on-line motor starter: contactor, overload relay, short-circuit protection and cable. Choose IEC (IEC 60947-4-1, IEC 60364) or NEC Article 430 rules with Table 430.250 motor current.
DOL Starter Component Calculator
How to Use DOL Starter Component Calculator
- 1Choose the standard. IEC gives an AC-3 contactor, overload setting, MCB or MPCB and a mm² cable. NEC gives the NEMA size, overload limits, Table 430.52 breaker maximum and an AWG conductor.
- 2Enter the motor. Power, phase and voltage. For NEC, enter HP at a nameplate voltage (115, 200, 208, 230, 460 or 575 V) so the table current is used.
- 3Add efficiency, power factor, margin and cable length. Catalogue efficiency and PF give a better IEC current. The margin only affects the contactor. A cable length above 30 m adds a voltage-drop reminder.
How to Calculate DOL Starter Components
A direct-on-line starter connects the motor straight to the supply, so every component sees the full line current, and the starting current (typically 6 to 8 × FLC) for the run-up time.
Single-phase: I = P × 1000 / (V × PF × η)
P in kW (1 HP = 0.746 kW), V = line voltage, PF = cos φ, η = efficiency as a decimal. Under the NEC, the controller, conductors and short-circuit protection are sized from Table 430.250 or 430.248 current (430.6(A)(1)); the overload uses the nameplate FLA (430.6(A)(2)).
| Component | IEC rule used | NEC rule used |
|---|---|---|
| Contactor / controller | AC-3 rated current ≥ FLC × margin (IEC 60947-4-1) | Horsepower rating ≥ motor HP at the voltage (430.83); NEMA size from NEMA ICS 2 |
| Overload relay | Set to motor rated current; trip class 10 for normal starts, 20 or 30 for long starts | Trip at no more than 125% of FLA (service factor ≥ 1.15 or temperature rise ≤ 40 °C), otherwise 115% (430.32(A)(1)) |
| Short-circuit protection | D-curve MCB ≥ 1.5 × FLC (a starting value), or an MPCB set to FLC; confirm with the Type 2 table | Inverse-time breaker ≤ 250% of FLC, time-delay fuse ≤ 175%; next standard size permitted (Table 430.52, 430.52(C)(1) Ex. 1, 240.6(A)) |
| Cable / conductors | Iz ≥ overload setting (IB ≤ In ≤ Iz, IEC 60364-4-43); Iz from IEC 60364-5-52 Table B.52.4, method C | Ampacity ≥ 125% of FLC (430.22), Table 310.16 75 °C copper |
| Disconnecting means | Isolator or switch-disconnector rated for the motor (IEC 60947-3, AC-23 for motor switching) | Ampere rating ≥ 115% of FLC and HP-rated (430.110(A), 430.109) |
With a separate overload relay, the cable is protected against overload by the relay, so the short-circuit device may be larger than the cable's Iz. The cable must still withstand the short-circuit let-through energy of that device (k²S² ≥ I²t).
IEC example: 7.5 kW, 400 V, three-phase
Contactor: 14.15 × 1.25 = 17.69 A → 18 A (AC-3)
Overload relay: set to 14.15 A, Class 10
Short-circuit device: 1.5 × 14.15 = 21.23 A → 25 A D-curve MCB, or an MPCB set to 14.15 A
Cable: Iz ≥ 14.15 A → 1.5 mm² Cu (17.5 A, method C, before derating)
If the cable runs in a group or in a hot location, apply the IEC 60364-5-52 correction factors and the size often rises to 2.5 mm². Check the voltage drop at starting current on long runs.
NEC example: 10 HP, 460 V, three-phase
Controller: HP rating ≥ 10 HP at 460 V → NEMA Size 1
Overload: set to nameplate FLA; maximum trip 1.25 × 14 = 17.5 A (if FLA = 14 A and SF = 1.15)
Inverse-time breaker: 2.5 × 14 = 35 A maximum (35 A is a 240.6(A) standard size)
Time-delay fuse: 1.75 × 14 = 24.5 A → 25 A
Conductors: 1.25 × 14 = 17.5 A → 14 AWG Cu (20 A at 75 °C)
Disconnect: ≥ 1.15 × 14 = 16.1 A, HP-rated
The 75 °C column may be used for motors marked with design letter B, C or D (110.14(C)(1)(a)(4)); otherwise check the terminal rating. The 15 A small-conductor limit of 240.4(D) does not apply to motor circuits (240.4(G)).
DOL Starter Component Sizing Reference Chart
IEC: 400 V three-phase (PF 0.85, efficiency 90%, 125% contactor margin)
| Motor (kW) | FLC (A) | Contactor (AC-3) | Overload setting (A) | MCB D-curve | Cable Cu, method C |
|---|---|---|---|---|---|
| 0.37 | 0.70 | 9 A | 0.70 | 6 A | 1.5 mm² |
| 0.75 | 1.42 | 9 A | 1.42 | 6 A | 1.5 mm² |
| 1.5 | 2.83 | 9 A | 2.83 | 6 A | 1.5 mm² |
| 2.2 | 4.15 | 9 A | 4.15 | 10 A | 1.5 mm² |
| 4 | 7.55 | 12 A | 7.55 | 16 A | 1.5 mm² |
| 5.5 | 10.38 | 18 A | 10.38 | 16 A | 1.5 mm² |
| 7.5 | 14.15 | 18 A | 14.15 | 25 A | 1.5 mm² |
| 11 | 20.75 | 32 A | 20.75 | 32 A | 2.5 mm² |
| 15 | 28.30 | 40 A | 28.30 | 50 A | 4 mm² |
| 18.5 | 34.91 | 50 A | 34.91 | 63 A | 6 mm² |
| 22 | 41.51 | 65 A | 41.51 | 63 A | 10 mm² |
| 30 | 56.60 | 80 A | 56.60 | 100 A | 10 mm² |
| 37 | 69.81 | 95 A | 69.81 | 125 A | 16 mm² |
NEC: 460 V three-phase (Table 430.250 FLC)
| Motor (HP) | FLC (A) | NEMA size | Max inverse-time CB | Max time-delay fuse | Conductor Cu 75 °C |
|---|---|---|---|---|---|
| 1 | 2.10 | 00 | 15 A | 6 A | 14 AWG |
| 2 | 3.40 | 00 | 15 A | 6 A | 14 AWG |
| 3 | 4.80 | 0 | 15 A | 10 A | 14 AWG |
| 5 | 7.60 | 0 | 20 A | 15 A | 14 AWG |
| 7.5 | 11.00 | 1 | 30 A | 20 A | 14 AWG |
| 10 | 14.00 | 1 | 35 A | 25 A | 14 AWG |
| 15 | 21.00 | 2 | 60 A | 40 A | 10 AWG |
| 20 | 27.00 | 2 | 70 A | 50 A | 10 AWG |
| 25 | 34.00 | 2 | 90 A | 60 A | 8 AWG |
| 30 | 40.00 | 3 | 100 A | 70 A | 8 AWG |
| 40 | 52.00 | 3 | 150 A | 100 A | 6 AWG |
| 50 | 65.00 | 3 | 175 A | 125 A | 4 AWG |
| 75 | 96.00 | 4 | 250 A | 175 A | 1 AWG |
| 100 | 124.00 | 4 | 350 A | 225 A | 2/0 AWG |
Cable and conductor sizes are before ambient, grouping and voltage-drop corrections. Real motors below about 4 kW usually have a lower PF and efficiency than assumed here, so use nameplate current where available.
Common DOL Starter Sizing Mistakes
- Overload set above the motor current. Set it to the nameplate current, not to the contactor rating or the breaker rating.
- B or C-curve MCB on a motor. The starting current can reach the magnetic trip band of a C-curve device; D-curve, MPCB or the coordinated device from the manufacturer's table is the usual choice.
- Mixing code tables. Under the NEC, conductors and breakers use the table FLC, while overloads use the nameplate FLA. Using the nameplate value for the breaker can give a device that trips on start.
- Ignoring the starting voltage drop. Starting current of 6 to 8 × FLC on a long or weak feeder can stall the motor or dip other loads. The supply authority may also limit direct-on-line starting above a certain size.
- Breaking capacity not checked. The MCB, MPCB or MCCB must have a breaking capacity (Icu / Icn, or UL interrupting rating) at least equal to the prospective fault current at the panel.
DOL Starter Component Frequently Asked Questions
A short-circuit protective device (MCB, MPCB, MCCB or fuses), a contactor, a thermal or electronic overload relay, start and stop push buttons, a control-circuit fuse or breaker, and the power cables. Under the NEC a disconnecting means is also required within sight of the controller (430.102).
Choose a relay whose adjustment range includes the motor nameplate current and set it to that current. Under the NEC, the relay must trip at no more than 125% of the nameplate FLA for motors with a service factor of 1.15 or more (or a temperature rise of 40 °C or less), and 115% for other motors (430.32(A)(1)).
Under the NEC, an inverse-time breaker may be up to 250% of the Table 430.250 current, rounded up to the next standard size if needed (Table 430.52). Under IEC practice, use the device in the manufacturer's Type 2 table; a D-curve MCB of about 1.5 to 2 × FLC or an MPCB set to FLC are common starting points.
Under the NEC, the conductor ampacity must be at least 125% of the table FLC (430.22). Under IEC 60364, the cable current-carrying capacity after correction factors must be at least the overload relay setting. Check the voltage drop, including at starting, on long runs.
No standard sets one limit. It depends on the supply strength, the voltage dip other loads can accept, the supply authority's rules and the mechanical shock the load can take. Small motors are almost always DOL; larger ones often use star-delta, a soft starter or a VFD to cut the starting current.
Standards and References
The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.
- IEC 60947-4-1 – Contactors and motor-starters: AC-3 ratings, overload trip classes, Type 1 and Type 2 coordination. Published by IEC.
- IEC 60947-2 and IEC 60898-1 – Circuit-breakers (MCCB, MPCB) and MCBs including B, C and D tripping curves. Published by IEC.
- IEC 60364-4-43 and IEC 60364-5-52 – Overcurrent protection of cables (IB ≤ In ≤ Iz) and current-carrying capacities (Table B.52.4). Published by IEC.
- NFPA 70 (NEC) – Article 430 (430.6, 430.22, 430.32, 430.52 and Table 430.52, 430.83, 430.102, 430.110, Tables 430.248 and 430.250), 240.6(A) standard ratings and Table 310.16 ampacities. Published by NFPA.
- NEMA ICS 2 and UL 508A – NEMA starter sizes and horsepower ratings; industrial control panels and SCCR. Published by NEMA and UL.
Related Calculators
Star Delta Starter Component Calculator
Calculate star delta starter components including main contactor, delta contactor, star contactor, overload relay, MCCB…
Open calculator Panel DesignSolar Panel Fuse Size Calculator
Size your solar PV DC fuses and overcurrent protection devices instantly.
Open calculator Advanced ToolsPower Factor Panel Component Calculator
Professional-grade sizing simulator for power factor correction panels.
Open calculator