DOL Starter Component Calculator

Size the parts of a direct-on-line motor starter: contactor, overload relay, short-circuit protection and cable. Choose IEC (IEC 60947-4-1, IEC 60364) or NEC Article 430 rules with Table 430.250 motor current.

By Nadeem Sial, Senior Electrical EngineerUpdated

DOL Starter Component Calculator

kW
Volts
%
cos φ
%
Meters

IEC: motor current from P / (√3 × V × PF × η). Contactor AC-3 rating ≥ motor current; overload relay set to motor current; cable Iz ≥ relay setting (IEC 60364-4-43).

How to Use DOL Starter Component Calculator

  1. 1
    Choose the standard. IEC gives an AC-3 contactor, overload setting, MCB or MPCB and a mm² cable. NEC gives the NEMA size, overload limits, Table 430.52 breaker maximum and an AWG conductor.
  2. 2
    Enter the motor. Power, phase and voltage. For NEC, enter HP at a nameplate voltage (115, 200, 208, 230, 460 or 575 V) so the table current is used.
  3. 3
    Add efficiency, power factor, margin and cable length. Catalogue efficiency and PF give a better IEC current. The margin only affects the contactor. A cable length above 30 m adds a voltage-drop reminder.

How to Calculate DOL Starter Components

A direct-on-line starter connects the motor straight to the supply, so every component sees the full line current, and the starting current (typically 6 to 8 × FLC) for the run-up time.

Three-phase: I = P × 1000 / (√3 × V × PF × η)
Single-phase: I = P × 1000 / (V × PF × η)

P in kW (1 HP = 0.746 kW), V = line voltage, PF = cos φ, η = efficiency as a decimal. Under the NEC, the controller, conductors and short-circuit protection are sized from Table 430.250 or 430.248 current (430.6(A)(1)); the overload uses the nameplate FLA (430.6(A)(2)).

ComponentIEC rule usedNEC rule used
Contactor / controllerAC-3 rated current ≥ FLC × margin (IEC 60947-4-1)Horsepower rating ≥ motor HP at the voltage (430.83); NEMA size from NEMA ICS 2
Overload relaySet to motor rated current; trip class 10 for normal starts, 20 or 30 for long startsTrip at no more than 125% of FLA (service factor ≥ 1.15 or temperature rise ≤ 40 °C), otherwise 115% (430.32(A)(1))
Short-circuit protectionD-curve MCB ≥ 1.5 × FLC (a starting value), or an MPCB set to FLC; confirm with the Type 2 tableInverse-time breaker ≤ 250% of FLC, time-delay fuse ≤ 175%; next standard size permitted (Table 430.52, 430.52(C)(1) Ex. 1, 240.6(A))
Cable / conductorsIz ≥ overload setting (IB ≤ In ≤ Iz, IEC 60364-4-43); Iz from IEC 60364-5-52 Table B.52.4, method CAmpacity ≥ 125% of FLC (430.22), Table 310.16 75 °C copper
Disconnecting meansIsolator or switch-disconnector rated for the motor (IEC 60947-3, AC-23 for motor switching)Ampere rating ≥ 115% of FLC and HP-rated (430.110(A), 430.109)

With a separate overload relay, the cable is protected against overload by the relay, so the short-circuit device may be larger than the cable's Iz. The cable must still withstand the short-circuit let-through energy of that device (k²S² ≥ I²t).

IEC example: 7.5 kW, 400 V, three-phase

FLC = 7500 / (1.732 × 400 × 0.85 × 0.90) = 14.15 A
Contactor: 14.15 × 1.25 = 17.69 A → 18 A (AC-3)
Overload relay: set to 14.15 A, Class 10
Short-circuit device: 1.5 × 14.15 = 21.23 A → 25 A D-curve MCB, or an MPCB set to 14.15 A
Cable: Iz ≥ 14.15 A → 1.5 mm² Cu (17.5 A, method C, before derating)

If the cable runs in a group or in a hot location, apply the IEC 60364-5-52 correction factors and the size often rises to 2.5 mm². Check the voltage drop at starting current on long runs.

NEC example: 10 HP, 460 V, three-phase

FLC from Table 430.250 = 14 A
Controller: HP rating ≥ 10 HP at 460 V → NEMA Size 1
Overload: set to nameplate FLA; maximum trip 1.25 × 14 = 17.5 A (if FLA = 14 A and SF = 1.15)
Inverse-time breaker: 2.5 × 14 = 35 A maximum (35 A is a 240.6(A) standard size)
Time-delay fuse: 1.75 × 14 = 24.5 A → 25 A
Conductors: 1.25 × 14 = 17.5 A → 14 AWG Cu (20 A at 75 °C)
Disconnect: ≥ 1.15 × 14 = 16.1 A, HP-rated

The 75 °C column may be used for motors marked with design letter B, C or D (110.14(C)(1)(a)(4)); otherwise check the terminal rating. The 15 A small-conductor limit of 240.4(D) does not apply to motor circuits (240.4(G)).

DOL Starter Component Sizing Reference Chart

IEC: 400 V three-phase (PF 0.85, efficiency 90%, 125% contactor margin)

Motor (kW)FLC (A)Contactor (AC-3)Overload setting (A)MCB D-curveCable Cu, method C
0.370.709 A0.706 A1.5 mm²
0.751.429 A1.426 A1.5 mm²
1.52.839 A2.836 A1.5 mm²
2.24.159 A4.1510 A1.5 mm²
47.5512 A7.5516 A1.5 mm²
5.510.3818 A10.3816 A1.5 mm²
7.514.1518 A14.1525 A1.5 mm²
1120.7532 A20.7532 A2.5 mm²
1528.3040 A28.3050 A4 mm²
18.534.9150 A34.9163 A6 mm²
2241.5165 A41.5163 A10 mm²
3056.6080 A56.60100 A10 mm²
3769.8195 A69.81125 A16 mm²

NEC: 460 V three-phase (Table 430.250 FLC)

Motor (HP)FLC (A)NEMA sizeMax inverse-time CBMax time-delay fuseConductor Cu 75 °C
12.100015 A6 A14 AWG
23.400015 A6 A14 AWG
34.80015 A10 A14 AWG
57.60020 A15 A14 AWG
7.511.00130 A20 A14 AWG
1014.00135 A25 A14 AWG
1521.00260 A40 A10 AWG
2027.00270 A50 A10 AWG
2534.00290 A60 A8 AWG
3040.003100 A70 A8 AWG
4052.003150 A100 A6 AWG
5065.003175 A125 A4 AWG
7596.004250 A175 A1 AWG
100124.004350 A225 A2/0 AWG

Cable and conductor sizes are before ambient, grouping and voltage-drop corrections. Real motors below about 4 kW usually have a lower PF and efficiency than assumed here, so use nameplate current where available.

Common DOL Starter Sizing Mistakes

  • Overload set above the motor current. Set it to the nameplate current, not to the contactor rating or the breaker rating.
  • B or C-curve MCB on a motor. The starting current can reach the magnetic trip band of a C-curve device; D-curve, MPCB or the coordinated device from the manufacturer's table is the usual choice.
  • Mixing code tables. Under the NEC, conductors and breakers use the table FLC, while overloads use the nameplate FLA. Using the nameplate value for the breaker can give a device that trips on start.
  • Ignoring the starting voltage drop. Starting current of 6 to 8 × FLC on a long or weak feeder can stall the motor or dip other loads. The supply authority may also limit direct-on-line starting above a certain size.
  • Breaking capacity not checked. The MCB, MPCB or MCCB must have a breaking capacity (Icu / Icn, or UL interrupting rating) at least equal to the prospective fault current at the panel.

DOL Starter Component Frequently Asked Questions

A short-circuit protective device (MCB, MPCB, MCCB or fuses), a contactor, a thermal or electronic overload relay, start and stop push buttons, a control-circuit fuse or breaker, and the power cables. Under the NEC a disconnecting means is also required within sight of the controller (430.102).

Choose a relay whose adjustment range includes the motor nameplate current and set it to that current. Under the NEC, the relay must trip at no more than 125% of the nameplate FLA for motors with a service factor of 1.15 or more (or a temperature rise of 40 °C or less), and 115% for other motors (430.32(A)(1)).

Under the NEC, an inverse-time breaker may be up to 250% of the Table 430.250 current, rounded up to the next standard size if needed (Table 430.52). Under IEC practice, use the device in the manufacturer's Type 2 table; a D-curve MCB of about 1.5 to 2 × FLC or an MPCB set to FLC are common starting points.

Under the NEC, the conductor ampacity must be at least 125% of the table FLC (430.22). Under IEC 60364, the cable current-carrying capacity after correction factors must be at least the overload relay setting. Check the voltage drop, including at starting, on long runs.

No standard sets one limit. It depends on the supply strength, the voltage dip other loads can accept, the supply authority's rules and the mechanical shock the load can take. Small motors are almost always DOL; larger ones often use star-delta, a soft starter or a VFD to cut the starting current.

Standards and References

The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.

  • IEC 60947-4-1 – Contactors and motor-starters: AC-3 ratings, overload trip classes, Type 1 and Type 2 coordination. Published by IEC.
  • IEC 60947-2 and IEC 60898-1 – Circuit-breakers (MCCB, MPCB) and MCBs including B, C and D tripping curves. Published by IEC.
  • IEC 60364-4-43 and IEC 60364-5-52 – Overcurrent protection of cables (IB ≤ In ≤ Iz) and current-carrying capacities (Table B.52.4). Published by IEC.
  • NFPA 70 (NEC) – Article 430 (430.6, 430.22, 430.32, 430.52 and Table 430.52, 430.83, 430.102, 430.110, Tables 430.248 and 430.250), 240.6(A) standard ratings and Table 310.16 ampacities. Published by NFPA.
  • NEMA ICS 2 and UL 508A – NEMA starter sizes and horsepower ratings; industrial control panels and SCCR. Published by NEMA and UL.
Nadeem Sial

Nadeem Sial

Senior Electrical Engineer

This calculator and technical guide were developed and verified by Nadeem Sial to ensure engineering and calculation precision. View Full Profile →

Related Calculators