Star Delta Starter Component Calculator
Size the main, delta and star contactors, overload relay, breaker and cables for a star-delta (wye-delta) motor starter to IEC 60947-4-1 or NEC Article 430.
Star Delta Starter Component Calculator
How to Use the Star Delta Starter Calculator
- 1Choose the standard. IEC uses the calculated current and IEC MCCB ratings. NEC uses the Table 430.250 full-load current (when the HP and voltage are in the table) and NEC 430.52 / 430.22(C) rules.
- 2Enter motor power and line voltage. Use kW or HP from the nameplate. The voltage is the supply line voltage, which must equal the motor's delta voltage (for example a 400 V Δ / 690 V Y motor on a 400 V supply).
- 3Enter efficiency and power factor. Use nameplate values if you have them. They are used for the IEC current and for NEC sizes that are not in Table 430.250.
- 4Read the results. Contactor ratings are AC-3 currents. The overload relay range must include the setting shown (0.58 × FLC). Then check the selection against the manufacturer's coordination table.
Star Delta Sizing Rules (IEC and NEC)
In a standard open-transition star-delta starter, the main contactor (KM1) feeds the winding starts U1-V1-W1, the delta contactor (KM2) connects the winding ends back to the line, and the star contactor (KM3) shorts the winding ends during start. The main and delta contactors and the overload relay therefore carry the winding (phase) current, which is FLC / √3 = 0.577 × FLC. In star, the line current and torque are one third of the direct-on-line values.
| Item | IEC selection | NEC selection |
|---|---|---|
| Motor current used | Calculated FLC (or nameplate In) | Table 430.250 FLC for conductors and protection (430.6(A)(1)); nameplate FLA for overloads (430.6(A)(2)) |
| Main and delta contactor | AC-3 rating ≥ 0.58 × FLC (IEC 60947-4-1) | Same current rule; the starter assembly must have an HP rating ≥ the motor HP (430.83) |
| Star contactor | AC-3 rating ≥ 0.33 × FLC | Same |
| Overload relay | Set at 0.58 × FLC, trip class 10 or 20 to suit run-up time | Set from 0.58 × nameplate FLA, within 430.32 limits |
| Short-circuit protection | MCCB In ≈ 1.5 × FLC (rule of thumb), or the SCPD from the Type 2 coordination table | Inverse-time breaker ≤ 250 % of FLC (Table 430.52); next standard size up allowed (430.52(C)(1) Exc. 1, 240.6(A)) |
| Cables | Line Ib = FLC; each of the 6 motor leads Ib = 0.58 × FLC; Ib ≤ In ≤ Iz (IEC 60364-4-43) | Line conductors ≥ 125 % of FLC; controller-to-motor conductors ≥ 72 % of FLC (430.22(C)) |
IEC Example: 30 kW, 400 V Motor
Main / delta = 0.58 × 56.6 = 32.8 A → 40 A AC-3 (32 A is too small)
Star = 0.33 × 56.6 = 18.7 A → 25 A AC-3
Overload relay set at 32.8 A → 32–50 A range
MCCB = 1.5 × 56.6 = 84.9 A → 100 A
Cable design current: line 56.6 A, each motor lead 32.8 A
NEC Example: 40 HP, 460 V Motor
Main / delta = 0.58 × 52 = 30.2 A → 32 A AC-3
Star = 0.33 × 52 = 17.2 A → 18 A AC-3
Overload relay ≈ 30.2 A (use 0.58 × nameplate FLA) → 23–32 A range
Inverse-time breaker ≤ 2.5 × 52 = 130 A → next standard size 150 A maximum
Line conductors ≥ 1.25 × 52 = 65 A; motor leads ≥ 0.72 × 52 = 37.4 A
The 30 kW and 40 HP motors have nearly the same output, but the NEC result uses the table current (52 A at 460 V) and a breaker sized up to 250 %, while the IEC result uses the calculated current at 400 V and a smaller MCCB.
Star Delta Starter Size Chart
IEC: 400 V, PF 0.85, Efficiency 90 %
| Motor (kW) | FLC (A) | Main & Delta (AC-3) | Star (AC-3) | OLR range (setting) | MCCB |
|---|---|---|---|---|---|
| 7.5 | 14.2 | 9 A | 6 A | 7–10 A (8.2) | 25 A |
| 11 | 20.8 | 18 A | 9 A | 9–13 A (12.0) | 32 A |
| 15 | 28.3 | 18 A | 12 A | 12–18 A (16.4) | 50 A |
| 18.5 | 34.9 | 25 A | 12 A | 16–24 A (20.2) | 63 A |
| 22 | 41.5 | 25 A | 18 A | 23–32 A (24.1) | 63 A |
| 30 | 56.6 | 40 A | 25 A | 32–50 A (32.8) | 100 A |
| 37 | 69.8 | 50 A | 25 A | 32–50 A (40.5) | 125 A |
| 45 | 84.9 | 50 A | 32 A | 32–50 A (49.2) | 160 A |
| 55 | 103.8 | 65 A | 40 A | 48–65 A (60.2) | 160 A |
| 75 | 141.5 | 95 A | 50 A | 80–93 A (82.1) | 250 A |
| 90 | 169.8 | 115 A | 65 A | 90–120 A (98.5) | 315 A |
| 110 | 207.5 | 150 A | 80 A | 110–150 A (120.4) | 315 A |
| 132 | 249.1 | 150 A | 95 A | 110–150 A (144.5) | 400 A |
NEC: 460 V, FLC from Table 430.250
| Motor (HP) | FLC (A) | Main & Delta (AC-3) | Star (AC-3) | OLR range (setting) | Max inverse-time CB | Conductors line / motor (A) |
|---|---|---|---|---|---|---|
| 10 | 14 | 9 A | 6 A | 7–10 A (8.1) | 35 A | 17.5 / 10.1 |
| 15 | 21 | 18 A | 9 A | 9–13 A (12.2) | 60 A | 26.3 / 15.1 |
| 20 | 27 | 18 A | 9 A | 12–18 A (15.7) | 70 A | 33.8 / 19.4 |
| 25 | 34 | 25 A | 12 A | 16–24 A (19.7) | 90 A | 42.5 / 24.5 |
| 30 | 40 | 25 A | 18 A | 16–24 A (23.2) | 100 A | 50.0 / 28.8 |
| 40 | 52 | 32 A | 18 A | 23–32 A (30.2) | 150 A | 65.0 / 37.4 |
| 50 | 65 | 40 A | 25 A | 32–50 A (37.7) | 175 A | 81.3 / 46.8 |
| 60 | 77 | 50 A | 32 A | 32–50 A (44.7) | 200 A | 96.3 / 55.4 |
| 75 | 96 | 65 A | 32 A | 48–65 A (55.7) | 250 A | 120.0 / 69.1 |
| 100 | 124 | 80 A | 50 A | 63–80 A (71.9) | 350 A | 155.0 / 89.3 |
| 125 | 156 | 95 A | 65 A | 80–93 A (90.5) | 400 A | 195.0 / 112.3 |
| 150 | 180 | 115 A | 65 A | 90–120 A (104.4) | 450 A | 225.0 / 129.6 |
| 200 | 240 | 150 A | 80 A | 110–150 A (139.2) | 600 A | 300.0 / 172.8 |
Values match the calculator. Contactor steps follow a common AC-3 rating series (9, 12, 18, 25, 32, 40, 50, 65, 80, 95, 115, 150 A ...); each manufacturer's series differs slightly. Overload ranges overlap, so the calculator picks the first range that contains the setting.
Selection Checklist
- Motor connection: six terminals (or a 12-lead wye-delta motor) with a delta voltage equal to the supply line voltage. A 230 V Δ / 400 V Y motor cannot be star-delta started on 400 V.
- Utilisation category: select contactors on their AC-3 rating at your voltage (IEC 60947-4-1). Use AC-4 ratings only if the starter will be inched or plugged.
- Coordination: Type 1 allows damage to the contactor and relay after a short circuit; Type 2 allows only light contact welding that can be separated, and the starter must work afterwards (IEC 60947-4-1). Use the manufacturer's tested Type 2 combination for the prospective fault current.
- Breaking capacity: MCCB Icu (and Ics) per IEC 60947-2, or the UL 489 interrupting rating, must be at least the prospective fault current at the panel. In UL 508A panels the starter combination sets the panel SCCR.
- Overload trip class: class 10 suits most motors; choose class 20 or 30 when the run-up time is long (high-inertia fans, loaded conveyors).
- Interlocking: star and delta contactors need electrical and, preferably, mechanical interlocking. A dedicated star-delta timer gives a short dead time between star opening and delta closing so the two never close together.
- Timer setting: the values shown are typical starting points only. Set the timer to the measured run-up time so the change to delta happens close to full speed; switching too early gives a current peak near DOL level.
Common Mistakes
- Setting the overload relay at the full line FLC when it is wired in the motor leads (it should be about 0.58 × FLC).
- Sizing the six motor leads for the full line current (oversized), or below 0.58 × FLC after derating (undersized).
- Using star-delta on loads that need high starting torque (loaded conveyors, positive-displacement pumps): star gives only one third of DOL torque, so the motor may not accelerate before the change to delta.
Star Delta Starter FAQs
They are connected in series with the motor windings, not in the supply line. In delta, the winding current is the line current divided by √3, which is 0.577 × FLC. They are selected on their AC-3 rating.
It only carries current during the star period. In star the winding voltage is 1/√3 of the delta value, so the line current is one third of the DOL starting current. Sizing at about 0.33 × FLC (AC-3) is the usual rule; some manufacturers use a larger star contactor for long or frequent starts.
When the relay is in the motor leads (after the main contactor), set it at 0.58 × the nameplate full-load current. If it is placed in the supply line before the starter, set it at the full nameplate current.
Under the NEC, an inverse-time breaker may be up to 250 % of the Table 430.250 FLC (Table 430.52), rounded up to the next standard rating. In IEC practice, use the SCPD given in the manufacturer's Type 2 coordination table; 1.5 × FLC is a common starting value for a thermal-magnetic MCCB.
When the supply or the utility limits the starting current and the load can start with one third of DOL torque, such as centrifugal fans and pumps started with valves or dampers closed. There is no fixed kW limit in IEC 60947-4-1 or the NEC; the limit usually comes from the utility or the supply transformer. For high-torque loads, use a soft starter or VFD instead.
Standards and References
The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.
- IEC 60947-4-1 – Contactors and motor-starters: AC-3 utilisation category, overload relay trip classes, Type 1 and Type 2 coordination. Published by IEC.
- IEC 60947-2 – Circuit-breakers, including Icu and Ics breaking capacities. Published by IEC.
- IEC 60364-4-43 – Protection against overcurrent (Ib ≤ In ≤ Iz). Published by IEC.
- NFPA 70 (NEC) Article 430 – 430.6(A), 430.22(C), 430.32, 430.52 and Table 430.52, 430.83, Table 430.250. Published by NFPA.
- NFPA 70 (NEC) 240.6(A) – Standard ampere ratings for fuses and inverse-time breakers. Published by NFPA.
- UL 489 and UL 508A – Molded-case circuit breakers; industrial control panels and SCCR. Published by UL.