Star Delta Starter Component Calculator

Size the main, delta and star contactors, overload relay, breaker and cables for a star-delta (wye-delta) motor starter to IEC 60947-4-1 or NEC Article 430.

By Nadeem Sial, Senior Electrical EngineerUpdated

Star Delta Starter Component Calculator

kW
Volts
%
cos φ

How to Use the Star Delta Starter Calculator

  1. 1
    Choose the standard. IEC uses the calculated current and IEC MCCB ratings. NEC uses the Table 430.250 full-load current (when the HP and voltage are in the table) and NEC 430.52 / 430.22(C) rules.
  2. 2
    Enter motor power and line voltage. Use kW or HP from the nameplate. The voltage is the supply line voltage, which must equal the motor's delta voltage (for example a 400 V Δ / 690 V Y motor on a 400 V supply).
  3. 3
    Enter efficiency and power factor. Use nameplate values if you have them. They are used for the IEC current and for NEC sizes that are not in Table 430.250.
  4. 4
    Read the results. Contactor ratings are AC-3 currents. The overload relay range must include the setting shown (0.58 × FLC). Then check the selection against the manufacturer's coordination table.

Star Delta Sizing Rules (IEC and NEC)

In a standard open-transition star-delta starter, the main contactor (KM1) feeds the winding starts U1-V1-W1, the delta contactor (KM2) connects the winding ends back to the line, and the star contactor (KM3) shorts the winding ends during start. The main and delta contactors and the overload relay therefore carry the winding (phase) current, which is FLC / √3 = 0.577 × FLC. In star, the line current and torque are one third of the direct-on-line values.

FLC = P × 1000 / (√3 × V × PF × η)   (P in kW; 1 HP = 0.746 kW)
ItemIEC selectionNEC selection
Motor current usedCalculated FLC (or nameplate In)Table 430.250 FLC for conductors and protection (430.6(A)(1)); nameplate FLA for overloads (430.6(A)(2))
Main and delta contactorAC-3 rating ≥ 0.58 × FLC (IEC 60947-4-1)Same current rule; the starter assembly must have an HP rating ≥ the motor HP (430.83)
Star contactorAC-3 rating ≥ 0.33 × FLCSame
Overload relaySet at 0.58 × FLC, trip class 10 or 20 to suit run-up timeSet from 0.58 × nameplate FLA, within 430.32 limits
Short-circuit protectionMCCB In ≈ 1.5 × FLC (rule of thumb), or the SCPD from the Type 2 coordination tableInverse-time breaker ≤ 250 % of FLC (Table 430.52); next standard size up allowed (430.52(C)(1) Exc. 1, 240.6(A))
CablesLine Ib = FLC; each of the 6 motor leads Ib = 0.58 × FLC; Ib ≤ In ≤ Iz (IEC 60364-4-43)Line conductors ≥ 125 % of FLC; controller-to-motor conductors ≥ 72 % of FLC (430.22(C))

IEC Example: 30 kW, 400 V Motor

FLC = 30,000 / (1.732 × 400 × 0.85 × 0.90) = 56.6 A
Main / delta = 0.58 × 56.6 = 32.8 A → 40 A AC-3 (32 A is too small)
Star = 0.33 × 56.6 = 18.7 A → 25 A AC-3
Overload relay set at 32.8 A → 32–50 A range
MCCB = 1.5 × 56.6 = 84.9 A → 100 A
Cable design current: line 56.6 A, each motor lead 32.8 A

NEC Example: 40 HP, 460 V Motor

FLC from Table 430.250 (40 HP, 460 V) = 52 A
Main / delta = 0.58 × 52 = 30.2 A → 32 A AC-3
Star = 0.33 × 52 = 17.2 A → 18 A AC-3
Overload relay ≈ 30.2 A (use 0.58 × nameplate FLA) → 23–32 A range
Inverse-time breaker ≤ 2.5 × 52 = 130 A → next standard size 150 A maximum
Line conductors ≥ 1.25 × 52 = 65 A; motor leads ≥ 0.72 × 52 = 37.4 A

The 30 kW and 40 HP motors have nearly the same output, but the NEC result uses the table current (52 A at 460 V) and a breaker sized up to 250 %, while the IEC result uses the calculated current at 400 V and a smaller MCCB.

Star Delta Starter Size Chart

IEC: 400 V, PF 0.85, Efficiency 90 %

Motor (kW)FLC (A)Main & Delta (AC-3)Star (AC-3)OLR range (setting)MCCB
7.514.29 A6 A7–10 A (8.2)25 A
1120.818 A9 A9–13 A (12.0)32 A
1528.318 A12 A12–18 A (16.4)50 A
18.534.925 A12 A16–24 A (20.2)63 A
2241.525 A18 A23–32 A (24.1)63 A
3056.640 A25 A32–50 A (32.8)100 A
3769.850 A25 A32–50 A (40.5)125 A
4584.950 A32 A32–50 A (49.2)160 A
55103.865 A40 A48–65 A (60.2)160 A
75141.595 A50 A80–93 A (82.1)250 A
90169.8115 A65 A90–120 A (98.5)315 A
110207.5150 A80 A110–150 A (120.4)315 A
132249.1150 A95 A110–150 A (144.5)400 A

NEC: 460 V, FLC from Table 430.250

Motor (HP)FLC (A)Main & Delta (AC-3)Star (AC-3)OLR range (setting)Max inverse-time CBConductors line / motor (A)
10149 A6 A7–10 A (8.1)35 A17.5 / 10.1
152118 A9 A9–13 A (12.2)60 A26.3 / 15.1
202718 A9 A12–18 A (15.7)70 A33.8 / 19.4
253425 A12 A16–24 A (19.7)90 A42.5 / 24.5
304025 A18 A16–24 A (23.2)100 A50.0 / 28.8
405232 A18 A23–32 A (30.2)150 A65.0 / 37.4
506540 A25 A32–50 A (37.7)175 A81.3 / 46.8
607750 A32 A32–50 A (44.7)200 A96.3 / 55.4
759665 A32 A48–65 A (55.7)250 A120.0 / 69.1
10012480 A50 A63–80 A (71.9)350 A155.0 / 89.3
12515695 A65 A80–93 A (90.5)400 A195.0 / 112.3
150180115 A65 A90–120 A (104.4)450 A225.0 / 129.6
200240150 A80 A110–150 A (139.2)600 A300.0 / 172.8

Values match the calculator. Contactor steps follow a common AC-3 rating series (9, 12, 18, 25, 32, 40, 50, 65, 80, 95, 115, 150 A ...); each manufacturer's series differs slightly. Overload ranges overlap, so the calculator picks the first range that contains the setting.

Selection Checklist

  • Motor connection: six terminals (or a 12-lead wye-delta motor) with a delta voltage equal to the supply line voltage. A 230 V Δ / 400 V Y motor cannot be star-delta started on 400 V.
  • Utilisation category: select contactors on their AC-3 rating at your voltage (IEC 60947-4-1). Use AC-4 ratings only if the starter will be inched or plugged.
  • Coordination: Type 1 allows damage to the contactor and relay after a short circuit; Type 2 allows only light contact welding that can be separated, and the starter must work afterwards (IEC 60947-4-1). Use the manufacturer's tested Type 2 combination for the prospective fault current.
  • Breaking capacity: MCCB Icu (and Ics) per IEC 60947-2, or the UL 489 interrupting rating, must be at least the prospective fault current at the panel. In UL 508A panels the starter combination sets the panel SCCR.
  • Overload trip class: class 10 suits most motors; choose class 20 or 30 when the run-up time is long (high-inertia fans, loaded conveyors).
  • Interlocking: star and delta contactors need electrical and, preferably, mechanical interlocking. A dedicated star-delta timer gives a short dead time between star opening and delta closing so the two never close together.
  • Timer setting: the values shown are typical starting points only. Set the timer to the measured run-up time so the change to delta happens close to full speed; switching too early gives a current peak near DOL level.

Common Mistakes

  • Setting the overload relay at the full line FLC when it is wired in the motor leads (it should be about 0.58 × FLC).
  • Sizing the six motor leads for the full line current (oversized), or below 0.58 × FLC after derating (undersized).
  • Using star-delta on loads that need high starting torque (loaded conveyors, positive-displacement pumps): star gives only one third of DOL torque, so the motor may not accelerate before the change to delta.

Star Delta Starter FAQs

They are connected in series with the motor windings, not in the supply line. In delta, the winding current is the line current divided by √3, which is 0.577 × FLC. They are selected on their AC-3 rating.

It only carries current during the star period. In star the winding voltage is 1/√3 of the delta value, so the line current is one third of the DOL starting current. Sizing at about 0.33 × FLC (AC-3) is the usual rule; some manufacturers use a larger star contactor for long or frequent starts.

When the relay is in the motor leads (after the main contactor), set it at 0.58 × the nameplate full-load current. If it is placed in the supply line before the starter, set it at the full nameplate current.

Under the NEC, an inverse-time breaker may be up to 250 % of the Table 430.250 FLC (Table 430.52), rounded up to the next standard rating. In IEC practice, use the SCPD given in the manufacturer's Type 2 coordination table; 1.5 × FLC is a common starting value for a thermal-magnetic MCCB.

When the supply or the utility limits the starting current and the load can start with one third of DOL torque, such as centrifugal fans and pumps started with valves or dampers closed. There is no fixed kW limit in IEC 60947-4-1 or the NEC; the limit usually comes from the utility or the supply transformer. For high-torque loads, use a soft starter or VFD instead.

Standards and References

The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.

  • IEC 60947-4-1 – Contactors and motor-starters: AC-3 utilisation category, overload relay trip classes, Type 1 and Type 2 coordination. Published by IEC.
  • IEC 60947-2 – Circuit-breakers, including Icu and Ics breaking capacities. Published by IEC.
  • IEC 60364-4-43 – Protection against overcurrent (Ib ≤ In ≤ Iz). Published by IEC.
  • NFPA 70 (NEC) Article 430 – 430.6(A), 430.22(C), 430.32, 430.52 and Table 430.52, 430.83, Table 430.250. Published by NFPA.
  • NFPA 70 (NEC) 240.6(A) – Standard ampere ratings for fuses and inverse-time breakers. Published by NFPA.
  • UL 489 and UL 508A – Molded-case circuit breakers; industrial control panels and SCCR. Published by UL.
Nadeem Sial

Nadeem Sial

Senior Electrical Engineer

This calculator and technical guide were developed and verified by Nadeem Sial to ensure engineering and calculation precision. View Full Profile →

Related Calculators

Panel Design

Star Delta Contactor Size Calculator

Calculate main contactor, delta contactor and star contactor ratings for star-delta starters using motor power and voltage.

Open calculator
Panel Design

DOL Starter Component Calculator

Calculate DOL starter components including standard AC-3 contactors, overload relay setting range, MCB/MCCB breakers…

Open calculator
Advanced Tools

Power Factor Panel Component Calculator

Professional-grade sizing simulator for power factor correction panels.

Open calculator