VFD Selection Calculator

Find the drive size and the output current a variable frequency drive needs for your motor, using IEC kW ratings or NEC HP ratings and Table 430.250 motor current.

By Nadeem Sial, Senior Electrical EngineerUpdated

VFD Selection Calculator

kW
Volts
Amps
%
cos φ

How to Use the VFD Selection Calculator

  1. 1
    Choose the standard. IEC gives the drive size in kW. NEC gives it in HP and, if you leave the FLA blank, uses the NEC Table 430.250 motor current for 200, 208, 230, 460 and 575 V (and the 220–240, 440–480 and 550–600 V ranges).
  2. 2
    Enter motor power, supply phase and voltage. The drive always feeds a three-phase motor; for single-phase input the motor voltage is normally the same as the supply (for example 230 V).
  3. 3
    Enter the nameplate FLA if you have it. Drive output current must cover the motor's actual current, and nameplate FLA is more accurate than a calculated value.
  4. 4
    Pick the application and sizing factor. 1.00 for fans and centrifugal pumps, 1.25 for constant-torque loads, 1.50 for high overload or high inertia.
  5. 5
    Check the current. Use the size as a guide, then confirm in the catalogue that the drive's output current is at least the "Required Drive Output Current".

How VFD Sizing Works

A drive is selected on output current, not on kW or HP alone. Two motors of the same power can have different currents (pole number, efficiency, voltage), and the drive's current limit and overload capability are what protect it.

Motor current (if no nameplate): I = P × 1000 / (√3 × V × PF × η)
Required drive output current = motor FLA × sizing factor
Drive power rating ≥ motor kW (or HP) × sizing factor → next standard size

Normal Duty vs Heavy Duty

Most drives carry two ratings. The overload values below are typical catalogue values, not values fixed by a standard; check the drive's data sheet.

RatingTypical overloadTypical loadsSizing factor in this calculator
Normal duty (light overload)About 110 % for 60 sCentrifugal fans and pumps, HVAC1.00
Heavy duty (high overload)About 150 % for 60 sConveyors, positive-displacement pumps and compressors, mixers1.25 (the HD rating is usually about one frame below the ND rating)
Above heavy dutyAbove 150 % or long overloadsCrushers, high-inertia fans, hoists1.50, then check with the manufacturer

IEC Example: 15 kW, 400 V Centrifugal Fan

I = 15,000 / (1.732 × 400 × 0.85 × 0.90) = 28.3 A (use nameplate FLA if known)
Sizing factor 1.00 → drive ≥ 15 kW, normal duty
Select a 15 kW drive whose normal-duty output current is at least 28.3 A

For a 15 kW conveyor (factor 1.25) the calculator gives 18.5 kW and a required normal-duty current of 35.4 A, or a heavy-duty current of at least 28.3 A.

NEC Example: 20 HP, 460 V Conveyor

FLC from Table 430.250 (20 HP, 460 V) = 27 A
Sizing factor 1.25 → 25 HP; required normal-duty current = 27 × 1.25 = 33.8 A
Select a 25 HP drive (ND current ≥ 33.8 A) or a drive whose heavy-duty current is ≥ 27 A
Input conductors ≥ 1.25 × the drive's rated input current from its nameplate (430.122(A))

Selection Checklist (IEC and NEC)

CheckWhat to doReference
Output currentDrive current at the chosen duty ≥ motor nameplate FLA × factorDrive data sheet; IEC 61800-2 ratings
DeratingReduce the drive's current for ambient above its rated value (often 40 °C), altitude above 1000 m and higher switching frequencyDrive manual
Single-phase supplyUse a drive rated for 1-phase input; a 3-phase-input drive on 1-phase needs a large deratingDrive manual
Input protectionNEC: conductors ≥ 125 % of drive input current (430.122(A)); disconnect ≥ 115 % (430.128); SCPD per 430.130 and the drive marking. IEC: the fuses or MCCB listed by the manufacturerNEC Art. 430 Part X; IEC 60364-4-43
Motor overloadDrive electronic overload can be used if the drive is marked for it (NEC 430.124). Several motors on one drive each need their own overload relayNEC 430.124; IEC 60364-4-43
Motor insulation and cable lengthLong motor cables cause reflected-wave overvoltage; use an inverter-duty motor or a dv/dt or sine filter as the manufacturer advisesNEMA MG 1 Part 31; IEC TS 60034-25
EMC and safetyChoose the EMC category for the site and install as the manual saysIEC 61800-3; IEC 61800-5-1 / UL 61800-5-1
HarmonicsCheck current distortion at the point of common coupling; add a line reactor, DC choke, multi-pulse or active front end if neededIEEE 519; IEC 61000-3-12
Panel SCCRDrive and its protective device must be rated for the available fault currentUL 508A; IEC 61439-1

VFD Size Chart

IEC: 400 V, PF 0.85, Efficiency 90 %

Motor (kW)Motor current (A)Fan / pump drive (factor 1.00)Constant torque drive (factor 1.25)Required ND current at 1.25 (A)
0.751.40.75 kW1.1 kW1.8
1.52.81.5 kW2.2 kW3.5
2.24.22.2 kW3 kW5.2
47.54 kW5.5 kW9.4
5.510.45.5 kW7.5 kW13.0
7.514.27.5 kW11 kW17.7
1120.811 kW15 kW25.9
1528.315 kW18.5 kW35.4
2241.522 kW30 kW51.9
3056.630 kW37 kW70.8
3769.837 kW55 kW87.3
55103.855 kW75 kW129.7
75141.575 kW110 kW176.9
110207.5110 kW160 kW259.4

NEC: 460 V, Motor Current from Table 430.250

Motor (HP)FLC (A)Fan / pump drive (factor 1.00)Constant torque drive (factor 1.25)Required ND current at 1.25 (A)
12.11 HP1.5 HP2.6
34.83 HP5 HP6.0
57.65 HP7.5 HP9.5
101410 HP15 HP17.5
152115 HP20 HP26.3
202720 HP25 HP33.8
304030 HP40 HP50.0
405240 HP50 HP65.0
506550 HP75 HP81.3
759675 HP100 HP120.0
100124100 HP125 HP155.0
150180150 HP200 HP225.0

Values match the calculator. Drive power steps are not evenly spaced, so a 1.25 factor sometimes jumps two sizes (for example 50 HP to 75 HP); in that case compare the current of the smaller drive's heavy-duty rating with the motor FLA before buying the larger one.

VFD Selection FAQs

Take the motor nameplate FLA, decide whether the load is normal duty or heavy duty, and choose a drive whose output current at that duty is at least the FLA (times any extra margin). Then apply the manufacturer's derating for ambient, altitude and switching frequency.

For fans and centrifugal pumps, a drive with the same normal-duty rating as the motor is usually right. For constant-torque or high-overload loads, use the drive's heavy-duty rating, which normally means the next larger drive.

Yes, with a drive rated for single-phase input and a 230 V three-phase motor. The input current is higher than the motor current. If you use a three-phase-input drive on single phase, the manufacturer's derating applies and is often large.

Yes, if they run at the same speed. The drive's output current must cover the sum of the motor currents, the drive must be set to V/f control, and each motor needs its own overload relay because the drive cannot protect motors individually.

NEC 430.122(A) requires the input conductors to have an ampacity of at least 125 % of the drive's rated input current, taken from the drive nameplate, not from the motor current.

IEC 61800-2 (ratings of low-voltage drives), IEC 61800-3 (EMC) and IEC 61800-5-1 (safety; UL 61800-5-1 in North America). Installation follows NEC Article 430 Part X or IEC 60364. IEEE 519 and IEC 61000-3-12 cover harmonics.

Standards and References

The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.

Nadeem Sial

Nadeem Sial

Senior Electrical Engineer

This calculator and technical guide were developed and verified by Nadeem Sial to ensure engineering and calculation precision. View Full Profile →

Related Calculators

Panel Design

VFD Energy Savings Calculator

Calculate VFD energy savings, power reduction, annual electricity cost savings and payback period for motors, pumps and…

Open calculator
Cable & Wires

Cable Selection Calculator

Calculate recommended electrical cable size based on load current, installation method, derating, voltage drop, and…

Open calculator
Panel Design

Breaker Size Calculator

Calculate the correct circuit breaker size for single-phase and three-phase electrical loads.

Open calculator