Contactor Size Calculator

Find the motor contactor size two ways: the IEC AC-3 rated current (IEC 60947-4-1) or the NEC/UL horsepower-rated NEMA starter size (NEC 430.83) using Table 430.250 motor current.

By Nadeem Sial, Senior Electrical EngineerUpdated

Contactor Size Calculator

kW
Volts
%
cos φ
%

IEC: current from P / (√3 × V × PF × η). The contactor's AC-3 rated operational current Ie at the supply voltage must be at least the motor rated current.

How to Use Contactor Size Calculator

  1. 1
    Choose the standard. IEC sizes by AC-3 rated current (IEC 60947-4-1). NEC sizes the controller by horsepower (NEC 430.83) and gives a NEMA starter size.
  2. 2
    Enter the motor. Power (kW or HP), supply voltage and phase. For NEC, enter HP at a nameplate voltage (115, 200, 208, 230, 460 or 575 V) so the calculator can use the code table current. If you know the current, tick the manual option.
  3. 3
    Set efficiency, power factor and margin. Use catalogue values for efficiency and PF. Leave the margin at 100% to get the smallest compliant size, or raise it for hot enclosures or frequent starts.

How to Calculate Contactor Size

1. Motor current

Three-phase: I = P × 1000 / (√3 × V × PF × η)
Single-phase: I = P × 1000 / (V × PF × η)

P in kW (1 HP = 0.746 kW), V in volts, PF = cos φ, η = efficiency as a decimal. Under the NEC, use the full-load current from Table 430.250 (three-phase) or Table 430.248 (single-phase) instead of the nameplate or a calculated value when sizing the controller rating, conductors and short-circuit protection (NEC 430.6(A)(1)). The table values apply to the voltage ranges 110–120, 220–240, 440–480 and 550–600 V.

2. Selection rule by standard

ItemIEC (IEC 60947-4-1)NEC / UL (NFPA 70 Art. 430)
Rating that must cover the motorRated operational current Ie for AC-3 at the supply voltage ≥ motor rated currentController horsepower rating ≥ motor HP at the application voltage (430.83(A)(1))
Motor current usedNameplate or catalogue current (or the formula above)Table 430.250 / 430.248 FLC (430.6(A)(1)); nameplate FLA for overloads (430.6(A)(2))
Typical deviceAC-3 rated contactor, frames such as 9, 12, 18, 25, 32, 40, 50, 65, 80, 95 ANEMA Size 00–9 starter (NEMA ICS 2), or a listed IEC-type contactor with UL HP ratings
Short-circuit coordinationType 1 or Type 2 with the stated SCPD (manufacturer tables)Listed combination and SCCR marking for industrial control panels (UL 508A)

3. Design margin

Neither IEC 60947-4-1 nor the NEC requires a 125% factor on the contactor. The 125% in NEC 430.22 applies to branch-circuit conductors, not the controller. A margin is a design choice: it buys longer electrical life, headroom for a hot enclosure, or room for a larger replacement motor. The calculator shows both the smallest compliant size (100%) and the size with your margin.

IEC example: 15 kW, 415 V, three-phase

FLC = 15000 / (1.732 × 415 × 0.85 × 0.90) = 27.28 A
Without margin: smallest AC-3 frame ≥ 27.28 A = 32 A
With 125% margin: 27.28 × 1.25 = 34.10 A → 40 A (AC-3)

Check the chosen contactor's AC-3 rating at 415 V in the catalogue. For a motor that is inched or plugged, use the manufacturer's AC-4 rating instead, which is lower for the same frame.

NEC example: 10 HP, 460 V, three-phase

FLC from Table 430.250 (460 V, 10 HP) = 14 A
Controller HP rating ≥ 10 HP at 460 V → NEMA Size 1 (27 A, 10 HP at 460 V)
IEC-type alternative: 14 × 1.25 = 17.5 A → 18 A AC-3 frame, provided its UL HP rating at 480 V is at least 10 HP

The same 10 HP motor on 230 V draws 28 A from the table and needs a NEMA Size 2, because Size 1 is rated only 7.5 HP at 230 V.

AC Utilisation Categories (IEC 60947-4-1)

The same contactor frame has different current ratings in each category. Always compare the motor current with the rating for the duty you actually have.

CategoryTypical loadWhat the contacts must handle
AC-1Non-inductive or slightly inductive loads, resistance heatersMake and break about rated current; highest current rating of the frame
AC-2Slip-ring motors: starting, switching offMake and break limited starting current
AC-3Squirrel-cage motors: starting, switching off while runningMake locked-rotor current, break about running current
AC-3eAs AC-3, for high-efficiency motors with higher locked-rotor current (added in the 2018 edition)Higher inrush than AC-3; relevant for IE3/IE4 motors (IEC 60034-30-1)
AC-4Squirrel-cage motors with plugging, inching or reversing from runningMake and break locked-rotor current; much shorter electrical life
AC-6bCapacitor banksHigh inrush; use capacitor-duty contactors

Contactor Size Calculator Chart

IEC: three-phase 400 V motors

Calculated with PF 0.85 and efficiency 90%. Small motors often have a lower PF and efficiency, so their real current is higher; use the nameplate value when you have it.

Motor (kW)Current (A)AC-3 frame, no marginCurrent × 1.25 (A)AC-3 frame, 125% margin
0.751.429 A1.779 A
2.24.159 A5.199 A
47.559 A9.4312 A
5.510.3812 A12.9718 A
7.514.1518 A17.6918 A
1120.7525 A25.9432 A
1528.3032 A35.3840 A
18.534.9140 A43.6350 A
2241.5150 A51.8965 A
3056.6065 A70.7580 A
3769.8180 A87.2695 A
4584.9095 A106.13115 A
55103.77115 A129.72150 A
75141.51150 A176.88185 A

Frame current steps follow a common catalogue series; some ranges use 38 A, 115 A or 330 A frames and others use different steps. Use the AC-3 kW or amp rating printed for your voltage.

NEC: Table 430.250 current and NEMA starter size

Motor (HP)FLC 230 V (A)NEMA size 230 VFLC 460 V (A)NEMA size 460 V
14.2002.100
39.604.80
515.217.60
7.5221111
10282141
15422212
20543272
25683342
30803403
501304653
751925964
10024851244
15036061805
20048062405

NEMA starter sizes (NEMA ICS 2, three-phase)

NEMA sizeContinuous ampsHP at 200 VHP at 230 VHP at 460 / 575 V
0091.51.52
018335
1277.57.510
245101525
390253050
41354050100
527075100200
6540150200400
7810–300600

The calculator uses the 200 V column for 208 V systems. Plugging or jogging duty needs a larger size; see the manufacturer's derating table.

Contactor Selection Checklist and Common Mistakes

  • Use the AC-3 (or HP) rating, not AC-1. The AC-1 current on the same frame is much higher than the AC-3 value and does not apply to motors.
  • Check the rating at your voltage. A frame rated 15 kW at 400 V carries a different kW rating at 230 V or 690 V; a NEMA Size 1 is 10 HP at 460 V but 7.5 HP at 230 V.
  • Match the duty. Inching, plugging and reversing are AC-4 duty. Many starts per hour or a long run-up time also shorten contact life.
  • Coordinate with the short-circuit device. Pick the contactor, overload relay and breaker or fuse from the same Type 2 table (IEC 60947-4-1) or a listed combination with a known SCCR (UL 508A).
  • Coil and auxiliaries. Specify the coil voltage and AC or DC supply, and the auxiliary contacts needed for the control circuit.
  • Enclosure temperature. Ratings apply up to a stated ambient. Check the derating if the panel runs hotter.
  • A contactor is not an isolator. Provide a separate disconnecting means (NEC 430.102 and 430.109; isolation requirements of IEC 60364-5-53).

Contactor Size Calculator Frequently Asked Questions

Find the motor full-load current (nameplate, catalogue or I = P / (√3 × V × PF × η)). Under IEC, choose a contactor whose AC-3 rated current at the supply voltage is at least that current. Under the NEC, use the Table 430.250 current and choose a controller whose horsepower rating at the supply voltage is at least the motor HP (430.83(A)(1)).

A 7.5 kW, 400 V motor draws about 14–15 A, so an 18 A AC-3 contactor is the usual choice. A 10 HP, 460 V motor has a table current of 14 A and needs a NEMA Size 1; at 230 V the table current is 28 A and it needs a NEMA Size 2.

AC-1 covers resistive loads such as heaters, where the contacts only make and break about rated current. AC-3 covers squirrel-cage motors, where the contacts must make the locked-rotor current. The AC-3 current for a given frame is therefore lower than its AC-1 current.

No standard requires it. IEC 60947-4-1 only needs the AC-3 rating to cover the motor current, and the NEC rates controllers by horsepower. The 125% rule in NEC 430.22 is for conductors. Many designers still add a margin for hot panels or frequent starting.

They are defined in IEC 60947-4-1 for the starter and its short-circuit device. After a short circuit, Type 1 allows damage to the contactor and overload relay as long as there is no danger to people. Type 2 requires the starter to remain fit for use, with only light contact welding that can be easily separated. Type 2 needs the exact breaker or fuse listed by the manufacturer.

Yes, if it is listed for the North American market and has a UL horsepower rating at your voltage that is at least the motor HP. Use the UL rating, not the IEC kW rating, and include the device in the panel's short-circuit current rating (SCCR) under UL 508A.

Standards and References

The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.

  • IEC 60947-4-1 – Low-voltage switchgear and controlgear: contactors and motor-starters (utilisation categories AC-1 to AC-4, Type 1 and Type 2 coordination). Published by IEC.
  • IEC 60034-30-1 – Efficiency classes (IE code) of line-operated AC motors. Published by IEC.
  • NFPA 70 (NEC) Article 430 – Motors and controllers: 430.6(A), 430.22, 430.83, 430.102, 430.109, Tables 430.248 and 430.250. Published by NFPA.
  • NEMA ICS 2 – Industrial control and systems: controllers, contactors and overload relays (NEMA starter sizes and horsepower ratings). Published by NEMA.
  • UL 60947-4-1 and UL 508A – Contactors and motor starters for North America, and industrial control panels including SCCR. Published by UL.
Nadeem Sial

Nadeem Sial

Senior Electrical Engineer

This calculator and technical guide were developed and verified by Nadeem Sial to ensure engineering and calculation precision. View Full Profile →

Related Calculators