Contactor Size Calculator
Determine the right IEC or NEC contactor for your motor applications, including derating and circuit protection.
Contactor Size Calculator
Results:
Calculated FLC (Full Load Current): 0.00 A
Required Derated Rating (Ie): 0.00 A
How to Use the Calculator
1. Select Standard
- Use the toggle at the top to choose between IEC and NEC standards.
- The required input fields will automatically adjust based on your selection.
2. Enter System Details
- Input your motor's power, system voltage, phase, and efficiency.
- For IEC, select the Utilization Category (e.g., AC-3).
- For NEC, provide the motor nameplate current and service factor.
3. Calculate & Review
- Apply any necessary derating factors for temperature, altitude, or grouping.
- Click "Calculate" to view the results.
- The tool will display the required ratings and further considerations based on your chosen standard.
How to Select & Size a Contactor (IEC Standards)
Selecting the correct IEC contactor involves more than just matching the motor's kW rating. This guide breaks down the essential steps, from defining the application and calculating the required current to ensuring proper short-circuit coordination and selecting the right accessories. Following these steps ensures a safe, reliable, and compliant installation.
1. Define Application & Duty
First, identify the load type to select the correct Utilization Category. This is critical for ensuring the contactor's endurance.
- AC-1: For resistive loads like heaters.
- AC-3: For standard squirrel-cage motors (most common).
- AC-4: For severe duty like jogging or plugging.
- AC-3e: For high-efficiency IE3/IE4 motors.
2. Establish System Ratings
Confirm your system's electrical characteristics to match the contactor's ratings.
- Ue: Rated Voltage (must be ≥ system voltage).
- Ui: Insulation Voltage (must be ≥ Ue).
- Uimp: Impulse Voltage (e.g., 6-8 kV).
IEC ratings assume <40°C ambient and <2000m altitude. Apply derating if conditions exceed this.
3. Size for Current (Ie)
Calculate the motor's Full Load Current (FLC), then apply all derating factors to find the required operational current (Ie).
Required Current Formula:
Ie = FLC / (kT × kalt × kG)Select a contactor where its standard Ie ≥ Required Ie.
4. Ensure Short-Circuit Coordination
This is a critical safety step. Select a coordination type based on your needs:
- Type 1: Contactor may be damaged after a fault.
- Type 2: No damage allowed, ensuring quick return to service.
Always use manufacturer-tested tables to select a contactor, overload, and SCPD (fuse/breaker) combination that is proven to work together.
5. Pair Overload Protection
A contactor does not protect against overloads. It must be paired with an overload relay.
- Setting: The relay's current range must include the motor's nameplate FLC.
- Trip Class: Use Class 10 for normal starts, or Class 20/30 for heavy loads with long acceleration times.
6. Select Control Coil
The coil is the electromagnet that activates the contactor.
- Voltage: Match the coil voltage (e.g., 24V DC, 230V AC) to your control circuit supply.
- Burden: Size the control transformer to handle the high inrush (pickup) VA, not just the sealed VA.
Consider low-consumption electronic coils if driving directly from a PLC.
7. Specify Accessories
Select any required add-ons for your application:
- Auxiliary Contacts: Add NO/NC contacts for status signals or control logic (e.g., seal-in circuit).
- Interlocks: Mechanical interlocks are mandatory for reversing starters.
- Terminals: Ensure terminals can fit your wire size and apply correct tightening torque.
8. Final Verification
Perform a final check before installation:
- Markings: Ensure the contactor is marked with IEC 60947-4-1 and all ratings (Ue, Ie, Ui, Uimp).
- Environment: Confirm the IP rating is suitable for the panel location.
- Endurance: For high-cycle duties, verify the electrical life meets your requirements.
Worked Example: Sizing an IEC Contactor
Scenario: Select a contactor for an 11 kW, 400V, 50 Hz IE3 motor with a nameplate Full Load Amp (FLA) of 20 A. The panel has an available fault current of 25 kA and the control circuit is 230V AC.
- Application & Duty: Standard IE3 motor, so the duty is AC-3. For better performance, we can also look for an AC-3e rating.
- Current Sizing (Ie): The motor FLA is 20 A. No derating is mentioned, so we need a contactor where its AC-3 rating at 400V is Ie ≥ 20 A. We would select the next standard size up for a safety margin.
- Short-Circuit Coordination: We need high reliability, so we select Type 2 coordination. We consult a manufacturer's coordination table for a 25 kA fault level. A typical tested combination might be:
- Contactor: Frame size rated for ~25A AC-3.
- Overload Relay: A model with a setting range that includes 20 A (e.g., 18-25 A), with Trip Class 10.
- SCPD: A 50 A aM type fuse or a specific MCCB model listed in the table.
- Control Circuit: We select a contactor with a 230V AC coil. We check its data sheet for inrush VA to size the control transformer correctly.
- Accessories: We will add a 1 NO + 1 NC auxiliary block for the seal-in circuit and a status signal to the PLC.
- Final Verification: The chosen contactor is marked with IEC 60947-4-1, its terminals accept our wire size, and its electrical endurance is suitable for the expected switching frequency.
Standard Derating Factors (IEC 60947)
Ambient Temperature
| Temperature | Derating Factor (kT) |
|---|---|
| Up to 40°C (104°F) | 1.0 |
| 50°C (122°F) | 0.95 |
| 55°C (131°F) | 0.90 |
| 60°C (140°F) | 0.85 |
Altitude
| Altitude | Derating Factor (kalt) |
|---|---|
| Up to 2000 m (6560 ft) | 1.0 |
| 2500 m (8200 ft) | 0.95 |
| 3000 m (9840 ft) | 0.90 |
| 4000 m (13120 ft) | 0.80 |
Grouping
| Condition | Factor (kG) |
|---|---|
| Single / Spaced | 1.0 |
| Tightly Grouped | 0.8 - 0.9 |
| Consult manufacturer for enclosed panels. | |
Contactor Size Chart (IEC vs. NEC)
This chart provides a quick reference for typical 3-phase motor contactor sizes. IEC values are based on AC-3 duty at 400V, while NEC values are based on HP ratings at 480V. Calculations assume PF=0.85 and Eff=0.90.
| Motor Power (kW) | Motor Voltage | Power Factor | Contactor Size (IEC) | Contactor Size (NEC) |
|---|---|---|---|---|
| 5.5 | 400V / 480V | 0.85 | AC-3, 12A | NEMA Size 1 |
| 6.5 | 400V / 480V | 0.85 | AC-3, 18A | NEMA Size 1 |
| 7.5 | 400V / 480V | 0.85 | AC-3, 18A | NEMA Size 1 |
| 8.5 | 400V / 480V | 0.85 | AC-3, 25A | NEMA Size 2 |
| 10 | 400V / 480V | 0.85 | AC-3, 25A | NEMA Size 2 |
| 11 | 400V / 480V | 0.85 | AC-3, 25A | NEMA Size 2 |
| 12.5 | 400V / 480V | 0.85 | AC-3, 32A | NEMA Size 2 |
| 15 | 400V / 480V | 0.85 | AC-3, 32A | NEMA Size 2 |
| 18.5 | 400V / 480V | 0.85 | AC-3, 40A | NEMA Size 2 |
| 20 | 400V / 480V | 0.85 | AC-3, 50A | NEMA Size 3 |
| 22 | 400V / 480V | 0.85 | AC-3, 50A | NEMA Size 3 |
| 25 | 400V / 480V | 0.85 | AC-3, 50A | NEMA Size 3 |
| 30 | 400V / 480V | 0.85 | AC-3, 65A | NEMA Size 3 |
| 34 | 400V / 480V | 0.85 | AC-3, 80A | NEMA Size 3 |
| 37 | 400V / 480V | 0.85 | AC-3, 80A | NEMA Size 3 |
| 40 | 400V / 480V | 0.85 | AC-3, 95A | NEMA Size 4 |
| 45 | 400V / 480V | 0.85 | AC-3, 95A | NEMA Size 4 |
| 50 | 400V / 480V | 0.85 | AC-3, 115A | NEMA Size 4 |
| 55 | 400V / 480V | 0.85 | AC-3, 115A | NEMA Size 4 |
| 60 | 400V / 480V | 0.85 | AC-3, 150A | NEMA Size 4 |
| 65 | 400V / 480V | 0.85 | AC-3, 150A | NEMA Size 4 |
| 70 | 400V / 480V | 0.85 | AC-3, 150A | NEMA Size 4 |
| 75 | 400V / 480V | 0.85 | AC-3, 150A | NEMA Size 4 |
| 80 | 400V / 480V | 0.85 | AC-3, 185A | NEMA Size 5 |
| 85 | 400V / 480V | 0.85 | AC-3, 185A | NEMA Size 5 |
| 90 | 400V / 480V | 0.85 | AC-3, 185A | NEMA Size 5 |
| 93 | 400V / 480V | 0.85 | AC-3, 225A | NEMA Size 5 |
| 95 | 400V / 480V | 0.85 | AC-3, 225A | NEMA Size 5 |
| 98 | 400V / 480V | 0.85 | AC-3, 225A | NEMA Size 5 |
| 100 | 400V / 480V | 0.85 | AC-3, 225A | NEMA Size 5 |
Quick IEC Compliance Checklist
Application & Duty
Confirm Utilization Category (AC-1, AC-3) matches the load.
System Ratings
Verify Ue, Ui, and Uimp ratings are suitable for the system.
Current Sizing
Ensure Ie rating is ≥ motor FLC after applying all derating.
Coordination
Select a Type 1 or Type 2 coordinated set from manufacturer tables.
Overload Relay
Pair with a relay that covers motor FLC and has the correct Trip Class.
Control Circuit
Match coil voltage to your control supply and size for inrush VA.
Quick NEC Compliance Checklist
Controller HP Rating
Contactor must have an HP rating ≥ the motor's HP at the operating voltage (NEC 430.83).
Conductors
Branch-circuit conductors must be sized to at least 125% of the motor's FLC from NEC tables.
Branch OCPD
Size the fuse or breaker according to NEC Table 430.52 (e.g., 250% for inverse-time breakers).
Overload Protection
Set the overload relay based on the motor's nameplate current (not table FLC), typically at 115% or 125%.
SCCR
The entire assembly's Short-Circuit Current Rating (SCCR) must be ≥ the available fault current at the panel.
Disconnecting Means
The disconnect switch must be rated for at least 115% of the motor's FLC.
Frequently Asked Questions
What size contactor for a 15kW motor?
For a 15 kW motor at 400V, the estimated Full Load Amps (FLA) is around 28 A. A standard IEC contactor for AC-3 duty would be a 32 A frame. If the contactor is in a hot environment (above 40°C) or grouped tightly with other components, you should select the next size up, such as a 40 A frame.
What size contactor for a 22kW motor?
A 22 kW motor has an estimated FLA of about 41-42 A. The typical IEC selection for AC-3 duty is a 50 A frame. For harsh conditions like high altitude or poor ventilation, it's wise to derate and use a 65 A frame.
What size contactor for a 30kW motor?
A 30 kW motor will have an FLA of approximately 56-57 A. The standard IEC pick for AC-3 duty is a 65 A frame. If you anticipate severe operating conditions, consider upsizing to an 80 A frame for reliability.
What size contactor for a 2.2kW motor?
A 2.2 kW motor has a small FLA of around 4.2 A. The typical IEC contactor for this size is a 9 A frame, which is a common small frame size. A 12 A frame would also work and provide extra headroom.
What is 13 and 14 on a contactor?
These numbers identify the terminals for a Normally Open (NO) auxiliary contact. The number pair 13-14 is used for a single NO contact, which is commonly used in control circuits for seal-in (latching), feedback signals, or electrical interlocks.
What is AC1, AC2, AC3, and AC4 duty?
These are IEC utilization categories that define the type of load a contactor is designed to switch:
- AC-1: The easiest duty, for non-inductive or slightly inductive loads like heaters.
- AC-2: For starting and stopping slip-ring motors.
- AC-3: The most common category, for starting squirrel-cage motors and switching them off after they reach full speed.
- AC-4: The most severe duty, for applications involving inching, jogging, or plugging (reversing) of squirrel-cage motors.
What is the load capacity of a 32 amp contactor?
The capacity depends on the utilization category:
- AC-1 Duty: It can handle 32 A of a resistive load.
- AC-3 Duty at 400V: It is typically suitable for a motor between 11 kW and 15 kW, which has an FLA of around 22-30 A. A 32 A AC-3 contactor is a good fit for a 15 kW motor in normal conditions.
Can I replace a 25 amp contactor with a 30 amp?
Yes, in most cases, this is a safe and often beneficial upgrade, as long as you verify a few key points:
- The coil voltage and frequency must match your control supply.
- It has the same number of main poles and auxiliary contacts that you need.
- It physically fits in the panel.
- Your short-circuit coordination (the tested combination of the contactor, overload, and fuse/breaker) is still valid.
What is T1, T2, T3 on a contactor?
T1, T2, and T3 are the load or output terminals of the contactor's main poles, which connect to the motor. The corresponding line or incoming supply terminals are typically labeled L1, L2, and L3.