BS 7671 Compliant UK EICR Ready Updated 2026

Ze Calculator

Determine external earth fault loop impedance (Ze) using measured loop impedance values and installation parameters in accordance with BS 7671.

⚡ Free Tool No Signup Instant Results
TX Substation External Path (Ze) MET Consumer Unit Ze = Zs − (R1 + R2)
BS 7671 Compliant
UK EICR Ready
Fast Ze Calculation

Ze Calculator

Ohms (Ω)

How to Use Ze Calculator

Determining the external earth fault loop impedance (Ze) is an essential part of verifying safety during initial installation verification and periodic inspection (EICR) testing. Follow these steps to use the calculator:

  • 1
    Select calculation mode. Choose "Measured Ze" if you have measured the value directly at the origin, or "Calculate from Zs and R1+R2" if you are using circuit parameters.
  • 2
    Enter measured values. Input the direct Ze value or enter the total measured loop impedance (Zs) and circuit conductor resistances (R1 + R2) in Ohms.
  • 3
    Click Calculate. Trigger the calculation engine to process the impedance values.
  • 4
    Review calculated Ze. View the final external loop impedance value displayed in Ohms.
  • 5
    Compare against typical UK supply characteristics. Check the installation assessment card to see if the value aligns with standard TN-C-S, TN-S, or TT earthing systems.
  • 6
    Use results during EICR or installation verification. Record the verified Ze on your electrical installation certificate or condition report.

How to Calculate Ze

External earth fault loop impedance (Ze) represents the impedance of the electrical path from the origin of the installation back to the substation transformer windings. It is a critical component of the total loop impedance, ensuring that protective devices operate within BS 7671 disconnection time limits during a fault.

Ze Calculation Formulas

Depending on your testing method, Ze is determined either by direct measurement or by calculation from total circuit impedance:

Formula 1 — Direct Measurement

Ze = Measured Earth Fault Loop Impedance (at Origin)

Formula 2 — Derivation from Zs

Ze = Zs − (R1 + R2)

Where:

  • Ze = External Earth Fault Loop Impedance (Ω)
  • Zs = Total Earth Fault Loop Impedance at the furthest point (Ω)
  • R1 + R2 = Sum of line and protective conductor (CPC) resistances (Ω)

Worked Example

Suppose you perform an inspection on a domestic ring main circuit and record the following parameters:

  • Measured Total Loop Impedance (Zs) = 0.68 Ω
  • Conductor Resistance (R1 + R2) = 0.22 Ω

Apply the subtraction formula to determine the external loop path:

Ze = 0.68 − 0.22
Ze = 0.46 Ω

Final Answer: Ze is calculated as 0.46 Ω.

Interpretation: Since this value is higher than 0.35 Ω, it exceeds the standard utility limit for a TN-C-S supply. However, it is within the 0.80 Ω limit allowed for a TN-S supply. The inspector should verify the earthing system type on-site to ensure full safety compliance.

Ze Chart

This table lists typical maximum permitted external loop impedance (Ze) limits for standard UK earthing systems under normal network conditions.

Supply Type Typical Maximum Ze (Ω) Description
TN-C-S 0.35 Ω Protective Multiple Earthing (PME) supply. Combined neutral and earth path.
TN-S 0.80 Ω Separate line, neutral, and earth conductor path from transformer.
TT 21.00 Ω Requires RCD protection. Relying on local ground electrode resistance.

Values should always be verified against the latest BS 7671 requirements and DNO information.

Ze Calculator Frequently Asked Questions

In UK electrical testing, Ze represents the external earth fault loop impedance measured at the origin of an installation, such as the main switch or consumer unit. It is the impedance of the external supply path, including the distributor's cables, substation transformer windings, and the earthing return path. Ze is verified under energized conditions with all bonding conductors disconnected to ensure a true external loop path.

Ze can be calculated by subtracting the protective conductor resistance of the line and CPC (R1 + R2) from the total measured earth fault loop impedance (Zs) at the end of the circuit, using the formula Ze = Zs - (R1 + R2). Alternatively, it can be measured directly at the origin of the installation with parallel paths temporarily isolated, which is the preferred method for initial verification under BS 7671.

A good Ze value is one that falls well within the standard limits set by the Distribution Network Operator (DNO) and BS 7671. For a TN-C-S (PME) supply, the Ze should not exceed 0.35 Ω. For a TN-S supply, the maximum limit is 0.80 Ω. For TT earthing systems, typical values are higher, but a stable earth electrode resistance (Ze) of under 21 Ω (ideally below 100 Ω) is recommended.

Under standard UK utility agreements and BS 7671, the maximum permitted external earth fault loop impedance (Ze) for a TN-C-S (Protective Multiple Earthing) supply is 0.35 Ω. If measurements exceed this value, it indicates a high-resistance fault in the DNO supply neutral/earth conductor, which must be immediately reported to the network provider for investigation and repair.

Ze is the external earth fault loop impedance measured at the origin of the installation (e.g., at the consumer unit) with parallel earth paths isolated. Zs is the total earth fault loop impedance measured at the furthest point of a specific circuit. The difference between them is the resistance of that circuit's line and earth conductors (R1 + R2), mathematically expressed as Zs = Ze + (R1 + R2).

Testing Ze during an Electrical Installation Condition Report (EICR) is vital to verify that the DNO's external earth connection is present and of low enough resistance. If the external earth is compromised or high resistance, the protective devices (MCBs, fuses) will not operate under fault conditions, leading to sustained hazardous touch voltages on exposed conductive parts of the property.

While Ze cannot definitively identify a supply type on its own, it provides a strong indication. A Ze of 0.35 Ω or less suggests a TN-C-S system. A Ze between 0.35 Ω and 0.80 Ω is typical of a TN-S supply. A Ze significantly higher than 0.80 Ω, such as 10 Ω or above, usually indicates a TT earthing system using local earth stakes. Physical inspection is always required for confirmation.

Ze should be tested during initial verification of any new installation, alteration, or addition, and during periodic inspections (EICR). For domestic properties, this is typically every 5 years or at change of occupancy. For commercial premises, it is every 5 years, and for industrial installations, it is every 3 years. It must also be checked if an earthing system anomaly is suspected.

Explore More UK Electrical Calculators

Zs Calculator

Calculate maximum permitted earth fault loop impedance (Zs) and verify disconnection times per BS 7671.

Calculate Zs →
🔧

R1 + R2 Calculator

Calculate end-of-line conductor resistances based on cable cross-sectional area, length, and temperature.

Calculate R1 + R2 →
🛠️

Earth Resistance Calculator

Determine ground electrode resistance and overall soil resistivity parameters for TT systems.

Calculate Earth Resistance →
🟢

Prospective Fault Current Calculator

Calculate maximum PFC and PSCC levels to verify protective device breaking capacities.

Calculate PFC →