Power Factor Calculator
Find power factor from kW and kVA, kW and kVAR, or measured voltage, current and kW on single-phase and three-phase supplies. The calculator also gives kVA, kVAR, the phase angle and the capacitor size needed to correct to 0.95.
How to Use the Power Factor Calculator
Pick the tab that matches the readings you have. Every tab also shows kVA, kVAR, the phase angle and the capacitor size needed to correct the load to 0.95.
- 1kW and kVA: use the real and apparent power from a power analyser or the utility bill.
- 2kW and kVAR: use this when your meter or bill shows reactive power instead of kVA.
- 3Volts, Amps and kW: choose single-phase or three-phase, then enter the measured voltage, current and real power. For three-phase, enter the line-to-line voltage and the line current.
- 4kVA and kVAR from PF: enter a load in kW and a known power factor (for example from a motor nameplate) to find the kVA a generator, transformer or cable must carry.
The result updates as you type. To size the correction capacitor bank in detail, continue with the Power Factor Correction Calculator.
How to Calculate Power Factor
Power factor is the ratio of real power, which does useful work, to apparent power, which is what the supply has to deliver. For sinusoidal voltage and current it equals the cosine of the angle φ between them.
Worked Example: Three-Phase Motor
A motor on a 400 V three-phase supply draws 50 A, and a power meter reads 28 kW.
- Apparent power: √3 × 400 × 50 ÷ 1000 = 34.64 kVA
- Power factor: 28 ÷ 34.64 = 0.808 (φ = 36.1°)
- Reactive power: √(34.64² − 28²) = 20.40 kVAR
- Capacitor to reach 0.95: 28 × (0.728 − 0.329) = 11.2 kVAR
After correction the same 28 kW is carried by 29.5 kVA instead of 34.6 kVA, so the line current falls from 50 A to about 42.5 A.
Lagging, Leading and Unity Power Factor
Lagging power factor means current lags voltage. It comes from inductive loads such as induction motors, transformers, fluorescent ballasts and welding sets, and it is by far the most common case in factories and buildings.
Leading power factor means current leads voltage. It appears when capacitor banks are oversized or left connected at light load, and with long lightly loaded cables. Over-correction can raise voltage and cause problems for generators, so correct to about 0.95 to 0.98 rather than exactly 1.
Unity power factor (1.0) means voltage and current are in phase. Resistive loads such as heaters and incandescent lamps run at unity.
With non-linear loads such as drives, rectifiers and switch-mode supplies, harmonics also lower the true power factor. Capacitors only fix the displacement part, so heavily distorted networks may need filters as well.
Power Factor Chart for a 100 kW Load
How kVA, kVAR, current and copper losses grow as power factor falls, for the same 100 kW of real power. Current and losses are shown relative to unity power factor.
| Power Factor | Apparent Power (kVA) | Reactive Power (kVAR) | Current vs PF 1.0 | I²R Losses vs PF 1.0 |
|---|---|---|---|---|
| 1.00 | 100.0 | 0.0 | 1.00× | 1.00× |
| 0.95 | 105.3 | 32.9 | 1.05× | 1.11× |
| 0.90 | 111.1 | 48.4 | 1.11× | 1.23× |
| 0.85 | 117.6 | 62.0 | 1.18× | 1.38× |
| 0.80 | 125.0 | 75.0 | 1.25× | 1.56× |
| 0.75 | 133.3 | 88.2 | 1.33× | 1.78× |
| 0.70 | 142.9 | 102.0 | 1.43× | 2.04× |
| 0.60 | 166.7 | 133.3 | 1.67× | 2.78× |
At 0.70 power factor the cables carry 43% more current and lose about twice as much energy as heat as they would at unity, for exactly the same useful power.
Typical Power Factor of Common Loads
Approximate values; check nameplates or measure for design work.
| Load | Typical Power Factor |
|---|---|
| Resistive heaters, incandescent lamps | 1.0 |
| Induction motor at full load | 0.80 – 0.90 |
| Induction motor at light load | 0.20 – 0.60 |
| Arc welders | 0.50 – 0.70 |
| Fluorescent lighting, uncorrected ballast | 0.50 – 0.60 |
| LED drivers and switch-mode supplies with PFC | 0.90 – 0.99 |
| Variable frequency drives (displacement PF) | 0.95 – 0.98 |
Lightly loaded motors are the most common cause of poor power factor, which is why right-sizing motors helps as much as adding capacitors.
Frequently Asked Questions (FAQs)
Most utilities and designers aim for 0.95 or higher. Many tariffs charge a penalty below 0.90 or 0.95, and values between 0.95 and 0.98 lagging are a practical target that avoids over-correction.
Work out apparent power first: kVA = V × I ÷ 1000 for single-phase, or √3 × V × I ÷ 1000 for three-phase. Then divide the real power in kW (from a power meter) by that kVA.
No. Real power can never exceed apparent power, so power factor ranges from 0 to 1. If your numbers give more than 1, the kW and kVA readings were taken at different times or one of them is wrong.
Inductive loads such as induction motors (especially when lightly loaded), transformers, welders and older lighting ballasts draw magnetising current that does no useful work, which lowers power factor.
Add capacitors close to inductive loads or an automatic capacitor bank at the main switchboard, avoid oversized motors running at light load, and use drives or equipment with built-in power factor correction.
For homes on a simple kWh tariff, usually not. Commercial and industrial customers are often billed on kVA demand, charged for excess kVARh, or given a surcharge when power factor falls below a threshold. The Power Factor Penalty Calculator estimates that cost.
Standards and References
The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.