Power Factor Penalty Calculator
Estimate how much a low power factor adds to your electricity bill. Choose your utility billing method (kVA demand adjustment, excess kVARh, percentage surcharge or kVAh billing) and see the monthly and yearly penalty plus the capacitor kVAR needed to avoid it.
How to Use the Power Factor Penalty Calculator
Utilities charge for poor power factor in different ways, so first find the method on your tariff or bill, then open the matching tab.
- 1kVA Demand Adjustment: your bill shows a demand charge in $/kW and a line such as "power factor adjustment" or "billed demand". Enter peak kW, actual power factor, the threshold and the demand charge.
- 2Excess kVARh: your meter records reactive energy (kVARh) and the tariff charges for kVARh above an allowance. Enter monthly kWh, average power factor, threshold and the rate per kVARh.
- 3Percentage Surcharge: the tariff adds a percentage to the bill for each 0.01 that power factor falls below the threshold.
- 4kVAh Billing: you are billed for apparent energy (kVAh) instead of kWh, so every unit of poor power factor is paid for directly.
Each tab also shows the yearly cost, which you can compare with the price of a capacitor bank from the Power Factor Correction Calculator.
How Power Factor Penalties Are Calculated
A low power factor makes the utility supply more current, and therefore bigger cables and transformers, for the same useful power. Tariffs recover that cost with one of four common methods.
1. kVA Demand Adjustment
Example: 500 kW peak demand at 0.78 power factor, a 0.90 threshold and a $12/kW demand charge. Billed demand = 500 × 0.90 ÷ 0.78 = 576.9 kW, so the penalty is 76.9 kW × $12 = $923 per month. About 159 kVAR of capacitors would bring the site to 0.90 and remove it.
2. Excess Reactive Energy (kVARh)
Example: 120,000 kWh at 0.80 power factor gives 90,000 kVARh. At a 0.90 threshold the allowance is 58,119 kVARh, so 31,881 kVARh are billed. At $0.015/kVARh the charge is $478 per month.
3. Percentage Surcharge
Example: a $15,000 bill, power factor 0.84 against a 0.90 threshold and a 1% surcharge per 0.01 step. That is 6 steps, so 6% or $900 per month.
4. kVAh Billing
Example: 50,000 kWh at 0.85 power factor is billed as 58,824 kVAh. At $0.12 per kVAh the poor power factor costs $1,059 per month compared with unity.
Power Factor Penalty Chart (0.90 Threshold)
Demand multiplier applied under the kVA demand adjustment method, and the extra demand billed on a 100 kW load.
| Actual PF | Demand Multiplier | Extra Billed Demand per 100 kW | Capacitor kVAR per 100 kW to Reach 0.90 |
|---|---|---|---|
| 0.90 or higher | 1.000 | 0 kW | 0 |
| 0.85 | 1.059 | 5.9 kW | 13.5 |
| 0.80 | 1.125 | 12.5 kW | 26.6 |
| 0.75 | 1.200 | 20.0 kW | 39.8 |
| 0.70 | 1.286 | 28.6 kW | 53.6 |
| 0.65 | 1.385 | 38.5 kW | 68.5 |
| 0.60 | 1.500 | 50.0 kW | 84.9 |
How to Reduce or Avoid Power Factor Penalties
- Install capacitor correction. Fixed capacitors on large, constantly running motors, or an automatic (APFC) bank at the main switchboard that switches steps as the load changes.
- Correct to 0.95–0.98, not 1.0. Over-correction gives a leading power factor at light load, which some utilities also penalise.
- Fix lightly loaded motors. Motors running far below rating have very poor power factor; right-sizing them or using drives helps.
- Watch for harmonics. With many drives or rectifiers, use detuned (reactor-protected) capacitor banks to avoid resonance.
- Check the payback. Divide the cost of the capacitor bank by the yearly penalty from this calculator; paybacks of one to three years are common.
Frequently Asked Questions (FAQs)
It is an extra charge that utilities apply to commercial and industrial customers whose power factor is below a threshold in the tariff, usually 0.90 or 0.95, to recover the cost of supplying the extra current.
Look at your tariff schedule or the bill itself. A "billed demand" or "power factor adjustment" line means demand adjustment, a kVARh line means reactive energy charges, a percentage line means a surcharge, and units billed in kVAh means kVAh billing.
Most tariffs start at 0.90; some use 0.85 or 0.95. Some utilities also give a small credit when power factor is above the threshold.
kVAR = kW × (tan(arccos actual PF) − tan(arccos target PF)). The demand adjustment tab shows this for your numbers; for example 500 kW at 0.78 needs about 159 kVAR to reach 0.90.
Almost never. Residential tariffs bill kWh only. Penalties apply to larger commercial and industrial connections with demand or reactive energy metering.
No. A demand charge is billed on your peak kW or kVA. A power factor penalty is an extra amount added when power factor is poor, often by increasing the billed demand.
Standards and References
The formulas and reference values on this page follow these standards. For design work, check results against the current edition that applies in your country and the equipment manufacturer's data.