Power Factor Correction Calculator
Optimize electrical efficiency and reduce energy costs
Power Factor Correction Calculator
IEEE 519 & IEC 61000 Standards Compliant
Correction Results:
Required Capacitors
Reactive Power: 0.00 kVAR
Capacitance: 0.00 μF
Current Analysis
Before Correction: 0.00 A
After Correction: 0.00 A
Current Reduction: 0.00%
Power Analysis
Apparent Power Before: 0.00 kVA
Apparent Power After: 0.00 kVA
kVA Reduction: 0.00%
Annual Savings
Energy Savings: $0.00
Demand Savings: $0.00
Total Annual Savings: $0.00
How to Use the Power Factor Correction Calculator
Step 1: System Information
- Select your system type (Single or Three Phase)
- Enter the real power consumption in kW
- Input the system voltage (line-to-line for 3-phase)
- Choose your system frequency (50Hz or 60Hz)
Tip: Use nameplate data or measured values for accuracy
Step 2: Power Factor Data
- Enter current power factor as decimal (0.75 = 75%)
- Set target power factor (typically 0.95)
- Input energy and demand charges from utility bill
- Click "Calculate" to get results
Note: Most utilities require PF ≥ 0.90 to avoid penalties
Step 3: Understanding Results
- kVAR: Required capacitive reactive power
- Capacitance: Total capacitor size needed
- Current Reduction: Decrease in line current
- Savings: Annual cost reduction potential
Important: Consider installation costs vs. savings
How Power Factor Correction Works
Power Factor Fundamentals
Power Factor (PF) = Real Power (kW) / Apparent Power (kVA)
Power factor represents the efficiency of electrical power usage. A low power factor means more current is required to deliver the same amount of useful power, resulting in:
- Higher electrical losses
- Increased utility demand charges
- Reduced system capacity
- Voltage regulation problems
Capacitive Correction
Capacitors provide leading reactive power to offset lagging reactive power from inductive loads:
- Motors and transformers create lagging power factor
- Capacitors create leading power factor
- Proper sizing neutralizes reactive power
- Result: Improved overall power factor
Detailed Calculation Example
Example: Industrial Motor Load
• Real Power: 100 kW
• Current Power Factor: 0.75
• Target Power Factor: 0.95
• System: 480V, 3-phase, 60Hz
Step 1: Calculate Current Reactive Power
θ₁ = arccos(0.75) = 41.41°
Q₁ = P × tan(θ₁) = 100 × tan(41.41°) = 88.19 kVAR
Step 2: Calculate Target Reactive Power
θ₂ = arccos(0.95) = 18.19°
Q₂ = P × tan(θ₂) = 100 × tan(18.19°) = 32.87 kVAR
Step 3: Required Capacitor Size
Qc = Q₁ - Q₂ = 88.19 - 32.87 = 55.32 kVAR
Step 4: Capacitance Calculation
C = Qc × 10⁶ / (2π × f × V²)
C = 55,320 × 10⁶ / (2π × 60 × 480²) = 638 μF
Power Factor Correction Formulas
Power Factor:
PF = cos(θ) = P / S
Required Capacitive Reactive Power:
Qc = P × (tan(θ₁) - tan(θ₂))
Capacitance (Single Phase):
C = Qc × 10⁶ / (2π × f × V²)
Capacitance (Three Phase):
C = Qc × 10⁶ / (3 × 2π × f × V²)
Current Reduction:
I₂ = I₁ × (PF₁ / PF₂)
Power Factor Reference Table
Power Factor | Angle (θ) | tan(θ) | Efficiency Rating |
---|---|---|---|
1.00 | 0° | 0.00 | Excellent |
0.95 | 18.2° | 0.33 | Very Good |
0.90 | 25.8° | 0.48 | Good |
0.85 | 31.8° | 0.62 | Fair |
0.80 | 36.9° | 0.75 | Poor |
0.70 | 45.6° | 1.02 | Very Poor |
Related Power Quality Calculators
Power Factor Calculator
Calculate power factor using voltage, current, and real power.
Try CalculatorTransformer Sizing Calculator
Calculates appropriate transformer capacity and specs based on load input.
Try Calculator